Daikin J Series Service Manual

Browse online or download Service Manual for Split-system air conditioners Daikin J Series. Daikin J Series Service manual User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 344
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews

Summary of Contents

Page 1 - J Series

SiE18-201J SeriesServiceManual[Applied Models]Super Multi Plus : Cooling Only Super Multi Plus : Heat Pump

Page 2 - Super Multi Plus

SiE18-201 Introduction ix 1.1.3 Inspection after Repair Be sure to use the specified cable to connect between the indoor and outdoor units. Make the

Page 3 - SiE18-201

SiE18-201 System controlMain Functions 893.17 Wet Protection Control IOutline When the outside air temperature is low, the lower limit of operating fr

Page 4 - Table of Contents iii

System control SiE18-20190 Main Functions3.18 Electric Parts Cooling and Electric Parts / Fin Temperature ControlOutline This function cools the elect

Page 5

SiE18-201 System controlMain Functions 913.19 Differential Pressure ControlOutline This function sets an upper limit for the fan rotation speed accord

Page 6 - Table of Contents v

System control SiE18-20192 Main Functions3.20 Year-Round Cooling-Only FunctionOutline This function turns off the compressor based on the conditions o

Page 7

SiE18-201 System controlMain Functions 933.21 Nighttime Low Noise ControlPurpose of the FunctionThis function lowers the operating sound when the nois

Page 8 - 1. Introduction

System control SiE18-20194 Main Functions3.22 PI ControlOutline Based on the ∆D signal, MAXα of the command frequency is monitored every 20 seconds, a

Page 9

SiE18-201 System controlMain Functions 953.23 Warm-Up FunctionOutline This function operates the inverter in a open-phase mode to warm up the compress

Page 10 - 1.1.3 Inspection after Repair

System control SiE18-20196 Main Functions3.24 Compressor Protection ControlPurpose of the FunctionThis function ensures appropriate compressor oil lev

Page 11 - 1.1.5 Using Icons List

SiE18-201 System controlMain Functions 973.25 Fan ControlPurpose of the FunctionThis function changes the fan rotation speed or stop the fan operation

Page 12 - List of Function

System control SiE18-20198 Main FunctionsFan control in normal heating modeDue to outside air temperature DOA and output frequency FOUT, conditions 

Page 13 - 1. List of Function

Introduction SiE18-201 x 1.1.4 Using Icons Icons are used to attract the attention of the reader to specific information. The meaning of each icon is

Page 14 - List of Function 3

SiE18-201 System controlMain Functions 993.26 Motorized Valve Control of Outdoor Unit3.26.1 Outline of Motorized Valve ControlOutline The EVL and EVG

Page 15 - : for FLK, FLX50/60J

System control SiE18-201100 Main Functions3.26.2 Outdoor Unit Motorized Valve Opening RestrictionOutline This function restricts the opening degree of

Page 16 - : for FLX50/60J

SiE18-201 System controlMain Functions 1013. EVL (liquid pipe motorized valve) opening restrictionEVL (liquid pipe motorized valve) ELV fully closed

Page 17 - 6 List of Function

System control SiE18-201102 Main Functions3.26.3 Outdoor Unit Motorized Valve Control in Startup and During the Number of Operating Room Units ChangeO

Page 18 - Specifications

SiE18-201 System controlMain Functions 103 In case of KBPIW 1.5 ≤ FPIMN / initial frequencyWhen initial frequency is equal or smaller than FPIMN / 1.

Page 19 - 1. Specifications

System control SiE18-201104 Main Functions3.26.5 Outdoor Units Motorized Valve Control by Target Discharge Pipe TemperatureOutline This function adjus

Page 20 - Indoor Unit

SiE18-201 System controlMain Functions 1053.27 Cooling Outdoor Unit SC ControlOutline This function controls the subcooling of the outdoor heat exchan

Page 21

System control SiE18-201106 Main Functions3.28 BP Unit Motorized Valve ControlPurpose of the FunctionThis function provides instructions regarding the

Page 22

SiE18-201 System controlMain Functions 1073.28.4 Full Closing of Motorized ValvesPurpose of the FunctionThe motorized valves are initialized when the

Page 23 - 1.1.2 Heat Pump

System control SiE18-201108 Main Functions3.28.6 Control Based on Relative Flow Rate InstructionPurpose of the FunctionThis function operates the moto

Page 24

SiE18-201 List of Function 1 Part 1List of Function 1. List of Function...

Page 25

SiE18-201 System controlMain Functions 1093.29 Gas Pipe Isothermal Control in Cooling OperationPurpose of the FunctionThis function ensures appropriat

Page 26

System control SiE18-201110 Main FunctionsThe motorized valve operating amount is determined based on deviation EGA between each room unit's gas

Page 27 - 1.2 BP Units

SiE18-201 System controlMain Functions 1113.30 SH Control in Cooling OperationPurpose of the FunctionThis function ensures appropriate refrigerant dis

Page 28 - 1.3 Indoor Units (for Europe)

System control SiE18-201112 Main FunctionsRegarding target superheated degree SH(Example) The following example is based on room A.When the sum of hea

Page 29 -  7.1kW Class

SiE18-201 System controlMain Functions 1133.31 SC Control in Heating OperationPurpose of the FunctionThis function ensures appropriate refrigerant dis

Page 30 -  Duct Connected Type

System control SiE18-201114 Main FunctionsDetails The heat exchanger intermediate temperature and liquid pipe temperature are detected at every sampli

Page 31 -  2.5kW Class · 3.5kW Class

SiE18-201 System controlMain Functions 1153.32 Heat Exchanger Isothermal Control in Heating OperationPurpose of the FunctionThis function ensures appr

Page 32

System control SiE18-201116 Main Functions3.33 BP Unit Motorized Valve Control in High Discharge Pipe TemperatureWhen the discharge pipe temperature e

Page 33 -  Floor Standing Type

SiE18-201 System controlMain Functions 1173.34 Inter-BP Units Heating Heat Exchanger Isothermal ControlPurpose of the FunctionThis function ensures ap

Page 34 - Connector Wiring Diagram

System control SiE18-201118 Main Functions3.35 Inter-BP Units Gas Pipe Isothermal ControlPurpose of the FunctionThis function ensures appropriate refr

Page 35 - Printed Circuit

List of Function SiE18-201 2 List of Function 1. List of Function 1.1 Function List for Europe R-22  1 : for FLX50/60J  2 – : for FLX50/60J Divi

Page 36

SiE18-201 System controlMain Functions 1193.36 BP Unit Motorized Valve Control by Target Discharge Pipe TemperaturePurpose of the FunctionThis functio

Page 37 - (Control PCB)

System control SiE18-201120 Main Functions3.37 4-Way Valve Operation3.37.1 4-Way Valve Operation SecurityPurpose of the FunctionThis function ensures

Page 38

SiE18-201 System controlMain Functions 1213.38 JIS ModePurpose of the FunctionThis aims to minimize capacity deviations at the time the JIS mode is de

Page 39 - FVX25 / 35K Series

System control SiE18-201122 Main Functions3.39 Pump Down OperationOutline When the Pump-down button is pressed, the following control is provided to c

Page 40 - Printed Circuit Board (1)~(3)

SiE18-201 System controlMain Functions 1233.40 Protection Control of SkyAir Indoor UnitsSkyAir Indoor Unit Peak-Cut ZoneThe zones for SkyAir indoor un

Page 41 - 1.4 FTXD50~71JV Series

System control SiE18-201124 Main FunctionsMonitoring Function During SkyAir Indoor Unit Heating Thermostat OFFIn the case of SkyAir indoor units, the

Page 42

SiE18-201Flow of Refrigerant 125Part 6Flow of Refrigerant1. Flow of Refrigerant...

Page 43

Flow of Refrigerant SiE18-201126 Flow of Refrigerant1. Flow of Refrigerant1.1 Flow of RefrigerantOperation ModeNo.Operating Status: Fixed opening (st

Page 44

SiE18-201 Flow of RefrigerantFlow of Refrigerant 1271.2 Standby Operation (Cooling)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTOR(

Page 45 - Other Designation

Flow of Refrigerant SiE18-201128 Flow of Refrigerant1.3 Equalizing Control (Cooling)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTOR

Page 46

SiE18-201 List of FunctionList of Function 31.2 Function List for Singapore, Malaysia, IndonesiaDivisionIndoor Unit / Outdoor UnitInverter (with Inver

Page 47

SiE18-201 Flow of RefrigerantFlow of Refrigerant 1291.4 Oil Return Operation (Cooling)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUT

Page 48 - Main Functions

Flow of Refrigerant SiE18-201130 Flow of Refrigerant1.5 Low Outside Air Temperature CoolingTHERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDIST

Page 49 - 1. Main Functions

SiE18-201 Flow of RefrigerantFlow of Refrigerant 1311.6 All-Room Operation (Cooling)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTOR

Page 50 - For FTX25/35 J

Flow of Refrigerant SiE18-201132 Flow of Refrigerant1.7 Multi-Room Operation (No Surplus Refrigerant) (Cooling)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORM

Page 51 - For FTK(X)25/35 J

SiE18-201 Flow of RefrigerantFlow of Refrigerant 1331.8 Multi-Room Operation (Cooling) (with Surplus Refrigerant)THERMISTORLIQUID PIPEOUTDOOR UNITMOTO

Page 52 - Detailed

Flow of Refrigerant SiE18-201134 Flow of Refrigerant1.9 1-Room Operation — Indoor Unit with Large Capacity (Cooling)THERMISTORLIQUID PIPEOUTDOOR UNITM

Page 53 - room temperature is at

SiE18-201 Flow of RefrigerantFlow of Refrigerant 1351.10 1-Room Operation — Indoor Unit with Small Capacity (2.5 kW) (Cooling)THERMISTORLIQUID PIPEOUT

Page 54 - 1.1.15 Intelligent Eye

Flow of Refrigerant SiE18-201136 Flow of Refrigerant1.11 Standby Operation (Heating)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTOR

Page 55 - Processing

SiE18-201 Flow of RefrigerantFlow of Refrigerant 1371.12 Equalizing Control (Heating)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTO

Page 56 - 1.1.17 Program Dry Operation

Flow of Refrigerant SiE18-201138 Flow of Refrigerant1.13 Oil Return Operation (Heating)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBU

Page 57 - Compressor OFF

List of Function SiE18-2014 List of Function1.3 Function List for Australia1  : for FLK, FLX50/60J2– : for FLK, FLX50/60JDivisionIndoor Unit / Outd

Page 58 - 1.1.22 Auto-Swing of Flap(s)

SiE18-201 Flow of RefrigerantFlow of Refrigerant 1391.14 Defrost Operation THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTOR(DEL)PROP

Page 59 - BLADE ANGLE

Flow of Refrigerant SiE18-201140 Flow of Refrigerant1.15 All-Room Operation (Heating)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBUTO

Page 60 - 1.1.26 Powerful Operation

SiE18-201 Flow of RefrigerantFlow of Refrigerant 1411.16 Multi-Room Operation (with non-Operating Room Unit) (Heating)THERMISTORLIQUID PIPEOUTDOOR UNI

Page 61 - 1.1.27 Filter Check Indicator

Flow of Refrigerant SiE18-201142 Flow of Refrigerant1.17 Multi-Room Operation (Heating)THERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FANDISTRIBU

Page 62 - 1.2 SkyAir

SiE18-201 Flow of RefrigerantFlow of Refrigerant 1431.18 1-Room Operation — Indoor Unit with Large Capacity (Heating)THERMISTORLIQUID PIPEOUTDOOR UNIT

Page 63 - 52 Main Functions

Flow of Refrigerant SiE18-201144 Flow of Refrigerant1.19 1-Room Operation — Indoor Unit with Small Capacity (2.5 kW) (Heating)THERMISTORLIQUID PIPEOUT

Page 64 - Cautions

SiE18-201Operations 145Part 7Operations1. Remote Controller...1461.1 Wirel

Page 65 - 54 Main Functions

Remote Controller SiE18-201146 Operations1. Remote Controller1.1 Wireless Remote Controller1.1.1 FTX25 / 35JCONAMPMAMPMTEMPON/OFFMODE -SLEEPSENSORO

Page 66 - OutdoorUnit / BP Unit

SiE18-201 Remote ControllerOperations 1471.1.2 FVX25 / 35KZOpen the cover.It displays the current settings.(In this illustration, eachsection is shown

Page 67 - 56 Main Functions

Remote Controller SiE18-201148 Operations1.1.3 FTXD25 / 35KZOpen the cover.It displays the current settings.(In this illustration, eachsection is show

Page 68 - Parts of Outdoor Unit

SiE18-201 List of FunctionList of Function 51.4 Function List for Europe R-407C1  : for FLX50/60J2– : for FLX50/60JDivisionIndoor Unit / Outdoor Un

Page 69 - 1.2 Major Functional Parts

SiE18-201 Remote ControllerOperations 1491.1.4 FTXD50 / 60 / 71JOpen the cover.It displays the current settings.(In this illustration, eachsection is

Page 70 - Main Functions 59

Remote Controller SiE18-201150 Operations1.1.5 FLX50 / 60JOpenthecover.CONAMPMAMPMPOWERFULMODEONCANCELOFFTEMPHOMELEAVESILENTFANSWINGTEMPON/OFFTransmit

Page 71 - 60 Main Functions

SiE18-201 Remote ControllerOperations 1511.1.6 CDX25 / 35 / 50 / 60J∗ARC423A13, ARC423A14 for CDK25 / 35 / 50 / 60HAVEC, CDX25 / 35 / 50 / 60HAVECCAMP

Page 72 - 2. Protection Device

Remote Controller SiE18-201152 Operations1.1.7 CDX25 / 35 / 50 / 60HACAMPMAMPMTEMPON/OFFMODEONOFFTIMERFA NCANCELPOWERFULLTransmitterIt sends signals t

Page 73 - 2.2 BP Unit

SiE18-201 Remote ControllerOperations 1531.1.8 FLX25 / 35H∗ARC423A9, ARC423A10 for FLK25 / 35 / 50 / 60HVEC, FLX25 / 35 / 50 / 60HVECCONAMPMAMPMTEMPON

Page 74 - 3. System control

Remote Controller SiE18-201154 Operations1.1.9 FHYC35 / 45 / 60 / 71B7V1 (Optional Accessory)BRC7C513WC

Page 75 - 3.2 Mode Configuration

SiE18-201 Remote ControllerOperations 155DISPLAY "▲" (SIGNALTRANSMISSION)DISPLAY " " (SET TEMPERA-TURE)DISPL

Page 76 - The Function

Remote Controller SiE18-201156 Operations1.2 Wired Remote Controller1.2.1 FHYC35 / 45 / 60 / 71B (Optional Accessory)BRC1C517REMOTE CONTROLLERNote For

Page 77 - Standby Operation

SiE18-201Operating Test 157Part 8Operating Test1. Operating Test ...1

Page 78 - 3.5 Equalizing Control

Operating Test SiE18-201158 Operating Test1. Operating Test1.1 Operating Test1OPERATING TEST*Check the connection status.Be sure to carry out initial

Page 79 - Equalizing Control in Heating

List of Function SiE18-2016 List of Function

Page 80

SiE18-201 Operating TestOperating Test 159*ex.) : Connect indoor units (2 rooms) to BP1.Connect indoor units (3 rooms) to BP2.Connect indoor units (2

Page 81

Operating Test SiE18-201160 Operating Test1. Record the installation location of each BP unit in the centralized name plate attached to the front pane

Page 82 - Main Functions 71

SiE18-201 Operating TestOperating Test 1611.2 Test Operation SwitchTEST OPERATION SWITCH [SW7]Press the FORCED OPERATION SWITCH [SW7]Aftrer sellecting

Page 83

Operating Test SiE18-201162 Operating Test1.3 Pump Down Operation Switch1. Close the liquid side stop valve of outdoor unit.2. Pump down3. Close the g

Page 84

SiE18-201 Operating TestOperating Test 1631.4 Record of the Installation PositionBe sure to enter the system unit installation position.1 SYSTEM LAYOU

Page 85 - 3.7 Oil Return Operation

Method of Field Set SiE18-201164 Operating Test2. Method of Field Set2.1 Field SettingWired Remote ControllerNotes: (Field setting must be made from t

Page 86 - Main Functions 75

SiE18-201 Method of Field SetOperating Test 165Wireless Remote ControllerNote: If optional accessories are mounted on the indoor unit, the indoor unit

Page 87 - 3.8 Defrost Operation

Method of Field Set SiE18-201166 Operating Test2.1.2 Local Setting Mode No.Example To set the filter sign time to “filter contamination - heavy” for a

Page 88 - Cooling standby operation

SiE18-201 Method of Field SetOperating Test 1673. When installing Sky Air simultaneous operation multi-unit, set to either “twin” or “triple.” Only wh

Page 89 - 3.10 Equalizing Control

Method of Field Set SiE18-201168 Operating TestWireless Setting (Address and MAIN/SUB Setting)ExplanationIf several wireless remote controller units a

Page 90 - Equalizing control in heating

SiE18-201Specifications 7Part 2Specifications1. Specifications...

Page 91 - 3.11 Capacity Control

SiE18-201 Method of Field SetOperating Test 169Setting the Address of Wireless Remote Controller (It is Factory Set to “1”) <Setting from the remot

Page 92 - Main Functions 81

Method of Field Set SiE18-201170 Operating TestAfter Setting Stick the Unit No. label at decoration panel air discharge outlet as well as on the back

Page 93 - 3.12 Peak Cut Control

SiE18-201 Method of Field SetOperating Test 171Fan Speed Changeover when Thermostat is OFFBy setting to “Set Fan Speed,” you can switch the fan speed

Page 94 - 3.13 Freeze-Up Prevention

Method of Field Set SiE18-201172 Operating Test2.2 Interface Adaptor for Room Airconditioner <KRP928A1S>Safety Precautions 3. Compatible Models4

Page 95 - 3.14 Gas Shortage Malfunction

SiE18-201 Method of Field SetOperating Test 173Note: Setting of Centralized Controller<DCS301B61, DCS302B61, KRC72>Please refer to Operating Ins

Page 96 - 3.15 Discharge Pipe Control

Method of Field Set SiE18-201174 Operating Test2.3 Precautions: For RMK140J / RMX140J Outdoor Unit UsersApplicable model seriesOutside air temperature

Page 97 - 3.16 Input Current Control

SiE18-201Service Diagnosis 175Part 9Service Diagnosis1. Troubleshooting - Split Type Indoor Unit...1761.1 Tr

Page 98

Troubleshooting - Split Type Indoor Unit SiE18-201176 Service Diagnosis1. Troubleshooting - Split Type Indoor Unit1.1 Troubleshooting with the Operati

Page 99 - 88 Main Functions

SiE18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 177Troubleshooting with the LED IndicationThere are green and red LEDs on the PCB.

Page 100 - 3.17 Wet Protection Control I

Troubleshooting - Split Type Indoor Unit SiE18-201178 Service Diagnosis1.2 Service Check Function1.2.1 ARC423 Series (FTX25/35J Series)In the ARC423A

Page 101 - Temperature Control

Specifications SiE18-2018 Specifications1. Specifications1.1 Outdoor Units1.1.1 Cooling OnlyNotes:1. ★ Refer to Engineering Data Book.2. The data are

Page 102 - Main Functions 91

SiE18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 1791.3 Code Indication on the Remote Controller1.3.1 Error Codes and Description o

Page 103

Troubleshooting - Split Type Indoor Unit SiE18-201180 Service Diagnosis1.4 Troubleshooting1.4.1 Indoor UnitsFTX25/35 J Series - : Not used for troubl

Page 104 - Function

SiE18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 1811.5 Troubleshooting Detail1.5.1 Faulty PCBRemote Controller DisplayA1Indoor Uni

Page 105 - 3.22 PI Control

Troubleshooting - Split Type Indoor Unit SiE18-201182 Service Diagnosis1.5.2 Operation Halt Due to the Freeze Protection FunctionRemote Controller Dis

Page 106 - 3.23 Warm-Up Function

SiE18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 183TroubleshootingCheck No.8Refer to P.254NONONOCheck No. 8Indoor unit heat exchan

Page 107

Troubleshooting - Split Type Indoor Unit SiE18-201184 Service Diagnosis1.5.3 Operation Halt Due to Fan Motor (AC Motor) or Related AbnormalityRemote C

Page 108 - 3.25 Fan Control

SiE18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 1851.5.4 Operation Halt Due to Detection of Thermistor or Related AbnormalityRemot

Page 109 - 3.25.2 Fan OFF Delay Control

Troubleshooting - Split Type Indoor Unit SiE18-201186 Service Diagnosis1.5.5 Faulty Indoor Unit PCBRemote Controller Display∗Indoor Unit LED DisplayA

Page 110 - EVG: Gas pipe motorized valve

SiE18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 1871.5.6 Faulty Indoor Unit PCBRemote Controller Display∗Indoor Unit LED DisplayA

Page 111

Troubleshooting - Split Type Indoor Unit SiE18-201188 Service Diagnosis1.5.7 Faulty Power Supply or Indoor Unit PCB (For FTK(X)25/35J)Remote Controlle

Page 112 - Main Functions 101

SiE18-201 Table of Contents i Super Multi PlusJ Series Heat PumpIndoor Unit FTX25JAV1NB FTXD50JV1B CDX25HAV1NB FLX25HV1NB FHYB35FK7V1FTX35JAV1NB FTX

Page 113 - 102 Main Functions

SiE18-201 SpecificationsSpecifications 9Notes:1. ★ Refer to Engineering Data Book.2. The data are based on the conditions shown in the table below.60H

Page 114 - Temperature

SiE18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 1891.5.8 Faulty Power Supply or Indoor Unit PCB (For FTK(X)50/60H, CDK(X)25~60H)Re

Page 115

Troubleshooting - Split Type Indoor Unit SiE18-201190 Service DiagnosisTroubleshootingCheck the varistor of the indoor unit PCB.Check the supply volta

Page 116 - Main Functions 105

SiE18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 191TroubleshootingCheck No.16Refer to P.258Check the voltage of the transformer&ap

Page 117

Troubleshooting - Split Type Indoor Unit SiE18-201192 Service Diagnosis1.5.9 Signal Transmission Error (Between Indoor and Outdoor Units)Remote Contro

Page 118 - Main Functions 107

SiE18-201 Troubleshooting - Split Type Indoor UnitService Diagnosis 1931.5.10 Signal Transmission Error (Between Indoor Unit and Remote Controller)Rem

Page 119

Troubleshooting - Split Type Indoor Unit SiE18-201194 Service DiagnosisTroubleshootingCheck the indoor unit's LED A.Check the outdoor unit's

Page 120

SiE18-201 Troubleshooting - SkyAir Indoor UnitService Diagnosis 1952. Troubleshooting - SkyAir Indoor Unit2.1 The INSPECTION/TEST ButtonExplanation By

Page 121

Troubleshooting - SkyAir Indoor Unit SiE18-201196 Service Diagnosis2.2 Self-Diagnosis by Wired Remote ControllerExplanation If operation stops due to

Page 122

SiE18-201 Troubleshooting - SkyAir Indoor UnitService Diagnosis 1972.3 Fault Diagnosis by Wireless Remote ControllerIf equipment stops due to a malfun

Page 123 - 112 Main Functions

Troubleshooting - SkyAir Indoor Unit SiE18-201198 Service DiagnosisNormal status1 Press INSPECTION/TEST button.If no button is pressedfor 1 minute, e

Page 124

Specifications SiE18-20110 SpecificationsNotes:1. ★ Refer to Engineering Data Book.2. The data are based on the conditions shows in the table below.50

Page 125 - 114 Main Functions

SiE18-201 Troubleshooting - SkyAir Indoor UnitService Diagnosis 1992.4 Troubleshooting by LED on the Indoor Unit’sForeword Troubleshooting can be carr

Page 126

Troubleshooting - SkyAir Indoor Unit SiE18-201200 Service Diagnosis2.5 Troubleshooting by Remote Controller Display / LED Display2.5.1 Explanation for

Page 127

SiE18-201 Troubleshooting - SkyAir Indoor UnitService Diagnosis 2012.6 Troubleshooting Detail2.6.1 Failure of Indoor Unit PC BoardRemote Controller Di

Page 128

Troubleshooting - SkyAir Indoor Unit SiE18-201202 Service Diagnosis2.6.2 Malfunction of Drain Water Level System (Float Type) Remote Controller Displa

Page 129

SiE18-201 Troubleshooting - SkyAir Indoor UnitService Diagnosis 203TroubleshootingCautionBe sure to turn off power switch before connect or disconnect

Page 130 - Pipe Temperature

Troubleshooting - SkyAir Indoor Unit SiE18-201204 Service Diagnosis2.6.3 Indoor Unit Fan Motor LockRemote Controller DisplayA6Applicable ModelsFHYCMet

Page 131 - 3.37 4-Way Valve Operation

SiE18-201 Troubleshooting - SkyAir Indoor UnitService Diagnosis 2052.6.4 Swing Flap Motor Malfunction / LockRemote Controller DisplayA7Applicable Mode

Page 132 - 3.38 JIS Mode

Troubleshooting - SkyAir Indoor Unit SiE18-201206 Service Diagnosis2.6.5 Failure of Capacity SettingRemote Controller DisplayAJApplicable ModelsFHYCMe

Page 133 - 3.39 Pump Down Operation

SiE18-201 Troubleshooting - SkyAir Indoor UnitService Diagnosis 2072.6.6 Malfunction of Heat Exchange Temperature Sensor System Remote Controller Disp

Page 134 - Unit Peak-Cut

Troubleshooting - SkyAir Indoor Unit SiE18-201208 Service Diagnosis2.6.7 Malfunction of Suction Air Temperature Sensor System Remote Controller Displa

Page 135 - 124 Main Functions

SiE18-201 SpecificationsSpecifications 11Notes:1. ★ Refer to Engineering Data Book.2. The data are based on the conditions shows in the table below.50

Page 136 - Flow of Refrigerant

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2093. Troubleshooting - Outdoor Unit Related3.1 The Unit Runs but Doesn’t Cool (Heat

Page 137 - 1. Flow of Refrigerant

Troubleshooting - Outdoor Unit Related SiE18-201210 Service DiagnosisTroubleshootingHeatingOpen the stop valve.There is possibility of EVn malfunction

Page 138 - Flow of Refrigerant 127

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2113.2 7 Seg. Display on the Outdoor P.C. BoardTROUBLE DAIGNOSIS <LED ON OUTDOOR

Page 139 - 128 Flow of Refrigerant

Troubleshooting - Outdoor Unit Related SiE18-201212 Service Diagnosis3.3 Troubleshooting Detail3.3.1 High Pressure MalfunctionOutdoor Unit IndicationE

Page 140 - Flow of Refrigerant 129

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2133.3.2 Compressor LockOutdoor Unit IndicationE6Method of Malfunction DetectionDete

Page 141 - 130 Flow of Refrigerant

Troubleshooting - Outdoor Unit Related SiE18-201214 Service Diagnosis3.3.3 Fan Lock / OvercurrentOutdoor Unit IndicationE7Method of Malfunction Detect

Page 142 - Flow of Refrigerant 131

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2153.3.4 Operation Halt Due to Detection of INV Input Current ErrorOutdoor Unit Indi

Page 143 - (Cooling)

Troubleshooting - Outdoor Unit Related SiE18-201216 Service Diagnosis3.3.5 Malfunction of Electronic Expansion ValveOutdoor Unit IndicationE9Method of

Page 144 - Refrigerant)

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2173.3.6 Operation Halt Due to Discharge Pipe Temperature ControlOutdoor Unit Indica

Page 145

Troubleshooting - Outdoor Unit Related SiE18-201218 Service Diagnosis3.3.7 LP Drop ErrorOutdoor Unit IndicationFCMethod of Malfunction DetectionWhen t

Page 146 - (2.5 kW) (Cooling)

Specifications SiE18-20112 Specifications1.1.2 Heat PumpNotes:1. ★ Refer to Engineering Data Book.2. The data are based on the conditions shown in the

Page 147 - 136 Flow of Refrigerant

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2193.3.8 Malfunction of High Pressure Switch SystemOutdoor Unit IndicationH3Method o

Page 148 - Flow of Refrigerant 137

Troubleshooting - Outdoor Unit Related SiE18-201220 Service Diagnosis3.3.9 Operation Halt Due to Faulty Position Detection SensorOutdoor Unit Indicati

Page 149 - 138 Flow of Refrigerant

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2213.3.10 Fan Position Detection ErrorOutdoor Unit IndicationH7Method of Malfunction

Page 150 - 1.14 Defrost Operation

Troubleshooting - Outdoor Unit Related SiE18-201222 Service Diagnosis3.3.11 Operation Halt Due to Detection of CT ErrorOutdoor Unit IndicationH8Method

Page 151 - 140 Flow of Refrigerant

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2233.3.12 Faulty Outside Air ThermistorOutdoor Unit IndicationH9Method of Malfunctio

Page 152 - (Heating)

Troubleshooting - Outdoor Unit Related SiE18-201224 Service Diagnosis3.3.13 Faulty Discharge ThermistorOutdoor Unit IndicationJ3Method of Malfunction

Page 153 - 142 Flow of Refrigerant

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2253.3.14 Faulty of Suction ThermistorOutdoor Unit IndicationJ5Method of Malfunction

Page 154

Troubleshooting - Outdoor Unit Related SiE18-201226 Service Diagnosis3.3.15 Faulty heat exchanger thermistorOutdoor Unit IndicationJ6Method of Malfunc

Page 155 - (2.5 kW) (Heating)

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2273.3.16 Faulty of Liquid Pipe ThermistorOutdoor Unit IndicationJ7Method of Malfunc

Page 156 - Operations

Troubleshooting - Outdoor Unit Related SiE18-201228 Service Diagnosis3.3.17 Faulty BP Liquid Pipe ThermistorOutdoor Unit IndicationJ8Method of Malfunc

Page 157 - 1. Remote Controller

SiE18-201 SpecificationsSpecifications 13Notes:1. ★ Refer to Engineering Data Book.2. The data are based on the conditions shown in the table below.60

Page 158 - 1.1.2 FVX25 / 35KZ

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2293.3.18 Faulty BP Gas Pipe ThermistorOutdoor Unit IndicationJ9Method of Malfunctio

Page 159 - 1.1.3 FTXD25 / 35KZ

Troubleshooting - Outdoor Unit Related SiE18-201230 Service Diagnosis3.3.19 Abnormal LP ErrorOutdoor Unit IndicationJCMethod of Malfunction Detection1

Page 160 - 1.1.4 FTXD50 / 60 / 71J

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2313.3.20 Rise in BOX TemperatureOutdoor Unit IndicationL3Method of Malfunction Dete

Page 161 - 1.1.5 FLX50 / 60J

Troubleshooting - Outdoor Unit Related SiE18-201232 Service Diagnosis3.3.21 Abnormal Rise in Fin TemperatureOutdoor Unit IndicationL4Method of Malfunc

Page 162 - 1.1.6 CDX25 / 35 / 50 / 60J

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2333.3.22 Operation Halt Due to Detection of Output OvercurrentOutdoor Unit Indicati

Page 163 - 1.1.7 CDX25 / 35 / 50 / 60HA

Troubleshooting - Outdoor Unit Related SiE18-201234 Service DiagnosisTroubleshootingCheck No.1Refer to P.249Check No.2Refer to P.249Check No.6Refer to

Page 164 - 1.1.8 FLX25 / 35H

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2353.3.23 Integrated Input Current StopOutdoor Unit IndicationL7Method of Malfunctio

Page 165 - BRC7C513WC

Troubleshooting - Outdoor Unit Related SiE18-201236 Service Diagnosis3.3.24 Electronic ThermalOutdoor Unit IndicationL8Method of Malfunction Detection

Page 166 - OPERATING SECTION (Fig. 1, 2)

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2373.3.25 Stall PreventionOutdoor Unit IndicationL9Method of Malfunction DetectionSt

Page 167 - 1.2 Wired Remote Controller

Troubleshooting - Outdoor Unit Related SiE18-201238 Service Diagnosis3.3.26 Transmission Error between MicrocomputersOutdoor Unit IndicationLCMethod o

Page 168 - Operating Test

Specifications SiE18-20114 SpecificationsNotes:1. ★ Refer to Engineering Data Book.2. The data are based on the conditions shown in the table below.50

Page 169 - 1. Operating Test

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2393.3.27 Overvoltage, Low VoltageOutdoor Unit IndicationU2Method of Malfunction Det

Page 170 - Operating Test 159

Troubleshooting - Outdoor Unit Related SiE18-201240 Service Diagnosis3.3.28 Transmission Error between Outdoor Unit and BP UnitOutdoor Unit Indication

Page 171 - INITIALIZE SETTING

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 241TroubleshootingCheck No.14Refer to P.257NOCould be outside causes other than erro

Page 172 - TEST OPERATION SWITCH [SW7]

Troubleshooting - Outdoor Unit Related SiE18-201242 Service Diagnosis3.3.29 Transmission Error between Indoor Unit and BP UnitOutdoor Unit IndicationU

Page 173 - ""

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2433.3.30 Transmission Error of DC FanOutdoor Unit IndicationU7Method of Malfunction

Page 174 - 1 SYSTEM LAYOUT

Troubleshooting - Outdoor Unit Related SiE18-201244 Service Diagnosis3.3.31 Operation Halt Due to Detection of Gas ShortageOutdoor Unit IndicationU0Me

Page 175 - 2. Method of Field Set

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 245TroubleshootingCheck No.3Refer to P.250CT CheckRefer to P.222NOCorrect connection

Page 176 - Wireless Remote Controller

Troubleshooting - Outdoor Unit Related SiE18-201246 Service Diagnosis3.3.32 System MalfunctionOutdoor Unit IndicationUHMethod of Malfunction Detection

Page 177 - 2.1.2 Local Setting Mode No

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2473.3.33 Faulty BOX Thermistor MalfunctionOutdoor Unit IndicationP3Method of Malfun

Page 178 - Filter Sign Setting

Troubleshooting - Outdoor Unit Related SiE18-201248 Service Diagnosis3.3.34 Faulty Fin ThermistorOutdoor Unit IndicationP4Method of Malfunction Detect

Page 179 - Receiver

SiE18-201 SpecificationsSpecifications 15Notes:1. ★ Refer to Engineering Data Book.2. The data are based on the conditions shows in the table below.50

Page 180

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2493.4 How to Check3.4.1 Installation Condition CheckCheck No.13.4.2 Discharge Press

Page 181

Troubleshooting - Outdoor Unit Related SiE18-201250 Service Diagnosis3.4.3 Electronic Expansion Valve CheckCheck No.3 Conduct the followings to check

Page 182

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2513.4.5 Internal Wiring Check (1)Check No.5 Check the wiring at the sections marked

Page 183 - <KRP928A1S>

Troubleshooting - Outdoor Unit Related SiE18-201252 Service Diagnosis3.4.6 Power Transistor Check (Capacitor Voltage Check)Check No.6 Power Transistor

Page 184 - 6. Function

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2533.4.7 Power Transistor Output CheckCheck No.7 Measure the output current and volt

Page 185 - These cases are not troubles

Troubleshooting - Outdoor Unit Related SiE18-201254 Service Diagnosis3.4.8 Thermistor Resistance CheckCheck No.8 Remove the connectors of the thermist

Page 186 - Service Diagnosis

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2553.4.9 Inverter Units Refrigerant System CheckCheck No.93.4.10 Inverter Units Inpu

Page 187 - Air outlet

Troubleshooting - Outdoor Unit Related SiE18-201256 Service Diagnosis3.4.11 Electrolytic Capacitor Capacity CheckCheck No.113.4.12 Voltage Check when

Page 188 - Indication

SiE18-201 Troubleshooting - Outdoor Unit RelatedService Diagnosis 2573.4.13 Power Supply Waveforms CheckCheck No.13 Measure the power supply waveform

Page 189 - 1.2 Service Check Function

Troubleshooting - Outdoor Unit Related SiE18-201258 Service Diagnosis3.4.15 Inverter Units Hall IC CheckCheck No.15 1. Check the connector connection.

Page 190

Specifications SiE18-20116 Specifications1.2 BP UnitsNote:1. BP or Indoor Unit Max. Height - BP or Indoor Unit Min. Height → Max. 15m.Set up BP and IU

Page 191 - 1.4 Troubleshooting

SiE18-201 BP Unit Trouble DiagnosisService Diagnosis 2594. BP Unit Trouble Diagnosis4.1 PCB Parts Layout4.2 LED On Branch Provider Unit (Diagnosis LED

Page 192 - 1.5 Troubleshooting Detail

BP Unit Trouble Diagnosis SiE18-201260 Service Diagnosis

Page 193 - 5 B 5

SiE18-201Removal Procedure 261Part 10Removal Procedure1. For BPMK928B42 · 43 ...2

Page 194

For BPMK928B42 · 43 SiE18-201262 Removal Procedure1. For BPMK928B42 · 431.1 Installation of Indoor UnitProcedure Warning Be sure to turn off all

Page 195

SiE18-201 For BPMK928B42 · 43Removal Procedure 2631.2 Opening of Electrical Box Cover and Removal of PCB MountProcedure Warning Be sure to turn o

Page 196 - C4, C5, C9, CA

For BPMK928B42 · 43 SiE18-201264 Removal Procedure2. Removing the PCB  The PCB is treated for moisture resistance. Replace the PCB and its mount toge

Page 197 - 1.5.5 Faulty Indoor Unit PCB

SiE18-201 For BPMK928B42 · 43Removal Procedure 2651.3 Removal of Motorized ValveProcedure Warning Be sure to turn off all power supplies before d

Page 198 - 1.5.6 Faulty Indoor Unit PCB

For BPMK928B42 · 43 SiE18-201266 Removal Procedure4. Dismounting the motorized valve Before taking this procedure, make sure there is no refrigerant

Page 199 - 188 Service Diagnosis

SiE18-201 For BPMK928B42 · 43Removal Procedure 2674Heat up the brazed sections of the motorized valve. Using pliers or the like, disconnect the valve.

Page 200 - CDK(X)25~60H)

For BPMK928B42 · 43 SiE18-201268 Removal Procedure1.4 Removal of ThermistorProcedure Warning Be sure to turn off all power supplies before disass

Page 201

SiE18-201 SpecificationsSpecifications 171.3 Indoor Units (for Europe)1.3.1 Heat Pump Wall Mounted Type★ Refer to Engineering Data Book. 2.5kW Class

Page 202

SiE18-201 For BPMK928B42 · 43Removal Procedure 2693Insert the new thermistor terminal to the thermistor connector. Align the thermistor terminal with

Page 203 - 5 B 3

Outdoor Unit SiE18-201270 Removal Procedure2. Outdoor Unit2.1 Removal of Outer PanelsProcedure Warning Be sure to wait 10 minutes or more after t

Page 204 - Controller)

SiE18-201 Outdoor UnitRemoval Procedure 2712.2 Removal of PCB and Electrical BoxProcedure Warning Be sure to wait 10 minutes or more after turnin

Page 205

Outdoor Unit SiE18-201272 Removal Procedure4. Disconnecting the compressor leads Handle the sound insulation with enough care. It may damage the pipe

Page 206 - Service Diagnosis 195

SiE18-201 Outdoor UnitRemoval Procedure 2735. Detaching the electrical box1Remove the screws from the electrical box.2Lift the electrical box off the

Page 207 - 196 Service Diagnosis

Outdoor Unit SiE18-201274 Removal Procedure3Disconnect the two relay connectors on the side.4Remove the two lock screws from the front section.5Slide

Page 208 - " DOWN " button

SiE18-201 Outdoor UnitRemoval Procedure 2757. Detaching the filter PCB1The filter PCB is located as shown at right.2Disconnect all the connectors and

Page 209 - 198 Service Diagnosis

Outdoor Unit SiE18-201276 Removal Procedure8. Detaching the control PCB1The control PCB is located as shown at right.2The setting and self-diagnostic

Page 210 - Maintenance

SiE18-201 Outdoor UnitRemoval Procedure 2775Remove the five locking card spacers and detach the control PCB. The back of the PCB has silicone compoun

Page 211 - 2.5.1 Explanation for Symbols

Outdoor Unit SiE18-201278 Removal Procedure11.Detaching the fan control PCB1The fan control PCB is located as shown at right.Remove the four locking c

Page 212 - 2.6 Troubleshooting Detail

Specifications SiE18-20118 Specifications★ Refer to Engineering Data Book. 5.0kW Class · 6.0kW Class50Hz 230VModelFTXD50JV1B FTXD60JV1BCooling Heatin

Page 213 - 202 Service Diagnosis

SiE18-201 Outdoor UnitRemoval Procedure 2792.3 Removal of Propeller Fans and Fan MotorsProcedure Warning Be sure to wait 10 minutes or more after

Page 214

Outdoor Unit SiE18-201280 Removal Procedure2. Dismounting the fan motors In disconnecting the connectors, do not pull the leads, but hold the connect

Page 215 - 204 Service Diagnosis

SiE18-201 Outdoor UnitRemoval Procedure 2812.4 Removal of ThermistorProcedure Warning Be sure to wait 10 minutes or more after turning off all po

Page 216 - Service Diagnosis 205

Outdoor Unit SiE18-201282 Removal Procedure2.5 Removal of Motorized ValveProcedure Warning Be sure to wait 10 minutes or more after turning off a

Page 217 - 206 Service Diagnosis

SiE18-201 Outdoor UnitRemoval Procedure 2834Disconnect the earth wire.WarningIf refrigerant gas leaks during the job, ventilate the room. (Bear in min

Page 218

Outdoor Unit SiE18-201284 Removal Procedure2.6 Removal of Sound InsulationProcedure Warning Be sure to wait 10 minutes or more after turning off

Page 219

SiE18-201 Outdoor UnitRemoval Procedure 2853Draw out the sound insulation cover from the bottom of the compressor.4Undo the two points of the sound in

Page 220 - Supposed

Outdoor Unit SiE18-201286 Removal Procedure2.7 Removal of CompressorProcedure Warning Be sure to wait 10 minutes or more after turning off all po

Page 221

SiE18-201 Outdoor UnitRemoval Procedure 2873Remove the three lock nuts from the compressor.4Remove the three lock bolts from the compressor. This is

Page 222 - Service Monitor

Outdoor Unit SiE18-201288 Removal Procedure2.8 Removal of 4-way ValveProcedure Warning Be sure to wait 10 minutes or more after turning off all p

Page 223 - 3.3 Troubleshooting Detail

SiE18-201 ii Table of Contents 1. Introduction ... vii 1.1 Sa

Page 224 - 3.3.2 Compressor Lock

SiE18-201 SpecificationsSpecifications 19 Duct Connected Type★ Refer to Engineering Data Book. 2.5kW Class · 3.5kW Class50Hz 230VModelCDX25HAV1NB CD

Page 225 - 3.3.3 Fan Lock / Overcurrent

SiE18-201 Outdoor UnitRemoval Procedure 2893Remove the lock screw from the piping assembly.4Disconnect the pipes form the accumulator (at points A and

Page 226 - Service Diagnosis 215

Outdoor Unit SiE18-201290 Removal Procedure7Cut off the compressor's discharge pipe (at point L) with the pipe cutter.8Disconnect the 4-way valve

Page 227 - 216 Service Diagnosis

SiE18-201 Outdoor UnitRemoval Procedure 2912. Disconnecting the 4-way valve1Remove the screw.2Get rid of the brazing at points A, B, C and D. Disconne

Page 228 - Service Diagnosis 217

Indoor Unit SiE18-201292 Removal Procedure3. Indoor Unit3.1 Refer following table for indoor unit removal procedureModel Number Service Manual PageFTX

Page 229 - 3.3.7 LP Drop Error

SiE18-201Caution Before Operation 293Part 11Cautions before Operation1. Installation...

Page 230 -  Faulty high pressure switch

Installation SiE18-201294 Caution Before Operation1. Installation1.1 Outdoor Unit1 INSTALLATION PROCEDURE1. Carrying-in• Ta ke care not to let your ha

Page 231 - 220 Service Diagnosis

SiE18-201 InstallationCaution Before Operation 295(C) Where there are obstacles on both suction and discharge sides: Pattern 1 Where the obstacles

Page 232 - Service Diagnosis 221

Installation SiE18-201296 Caution Before Operation1.2 BP UnitINSTALLATIONThree-sided view (product dimensions and attachment bolt pitch)• This unit ma

Page 233 - 222 Service Diagnosis

SiE18-201 InstallationCaution Before Operation 297Hanging bolt (M10 or M8)Six-sided nut (M10 or M8)Hanger metal 7Hanger metal 7Screws 8Screws

Page 234

Wiring SiE18-201298 Caution Before Operation2. Wiring2.1 Outdoor UnitELECTRIC WIRING CONNECTION1. Connection electric wire treatment ( CAUTION)Followi

Page 235

Specifications SiE18-20120 Specifications★ Refer to Engineering Data Book. 2.5kW Class · 3.5kW Class50Hz 230VModelCDX25JV1NB CDX35JV1NBCooling Heatin

Page 236

SiE18-201 WiringCaution Before Operation 2992. BP unit connection priorityWhen connecting to the BP unit, always start the connection with BP1 of the

Page 237

Wiring SiE18-201300 Caution Before Operation2.2 BP Unit• Connect refrigerant pipes and connection wires to the appropriate ports marked with matching

Page 238

SiE18-201 WiringCaution Before Operation 301(5) Follow the instruction on the wiring nameplate to connect the connection wires for indoor/outdoor unit

Page 239

Wiring SiE18-201302 Caution Before Operation2.3 Outdoor Unit Rotary Switch Setting* RAM View MonitorRSW1 RSW2 Remarks Unit00Latest (status) error code

Page 240

SiE18-201 WiringCaution Before Operation 303RSW1 RSW2 Remarks Unit41Current BP 1 Room-A gas pipe temperature Temp. offset 40h42Current BP 1 Room-B gas

Page 241 - 3.3.19 Abnormal LP Error

Others SiE18-201304 Caution Before Operation3. Others3.1 Explanation for FTX25/35J Series3.1.1 Test Run from the Remote Controller (For Heat Pump Mode

Page 242 - Service Diagnosis 231

SiE18-201 OthersCaution Before Operation 3053.1.2 Method of Operating Air Conditioners Individually (When Two Units are Installed in One Room) For Coo

Page 243 - 232 Service Diagnosis

Others SiE18-201306 Caution Before Operation3.1.5 Adjusting the Angle of the Intelligent-eye Sensor Once installation of the indoor unit is complete,

Page 244 - Service Diagnosis 233

SiE18-201 OthersCaution Before Operation 3073.2 Explanation for CDK(X)25~60H Series3.2.1 Test Run from the Remote Controller (For Heat Pump Model Only

Page 245

Others SiE18-201308 Caution Before Operation3.2.3 Centralized Control (For KRC72, KRP411A1S and KRP410A11S)For an explanation on usage, see the option

Page 246 - Service Diagnosis 235

SiE18-201 SpecificationsSpecifications 21 Floor / Ceiling Suspended Dual Type★ Refer to Engineering Data Book. 2.5kW Class · 3.5kW Class50Hz 230VMod

Page 247 - 3.3.24 Electronic Thermal

SiE18-201Appendix 309Part 12Appendix1. Piping Diagrams...3101.1 Outdoor

Page 248 - 3.3.25 Stall Prevention

Piping Diagrams SiE18-201310 Appendix1. Piping Diagrams1.1 Outdoor UnitsRMX140JVMB / RMX140JZVMBTHERMISTORLIQUID PIPEOUTDOOR UNITMOTORMOTORDC FANDC FA

Page 249 -  Faulty fan PC board

SiE18-201 Piping DiagramsAppendix 3111.2 BP UnitsBPMK928B42BPMK928B43REFRIGERANT FLOWOUTDOOR UNITOUTDOOR UNIT(19.1CuT)(9.5CuT)COOLINGHEATINGEXPANSION

Page 250 - Service Diagnosis 239

Piping Diagrams SiE18-201312 Appendix1.3 Indoor UnitsFTX25 / 35JAV1NBFTXD50 / 60 / 71JV1BFIELD PIPINGFIELD PIPINGCROSS FLOW FANFAN MOTORON HEAT EXCH.H

Page 251 - 240 Service Diagnosis

SiE18-201 Piping DiagramsAppendix 313CDX25 / 35 / 50 / 60HAV1NB, CDX25 / 35 / 50 / 60JV1NBFLX25 / 35HV1NBFIELD PIPINGFIELD PIPING( CuT)(6.4CuT) IN

Page 252

Piping Diagrams SiE18-201314 AppendixFLX50 / 60JV1B FHYB35 / 45 / 60 / 71FK7V1, FHYC35 / 45 / 60 / 71B7V1 ON INLET PIPEON HEAT EXCH.HEAT EXCHANGERSIRO

Page 253 - 242 Service Diagnosis

SiE18-201 Piping DiagramsAppendix 315FTK50 / 60HVEC, FTX50 / 60HVECFTXD25 / 35KZV1BHEAT EXCHANGERCROSS FLOW FANFAN MOTORFIELD PIPINGFIELD PIPING( A CU

Page 254 - Service Diagnosis 243

Piping Diagrams SiE18-201316 AppendixFVX25 / 35KZV1BFVX(K)35 12.7CuTFVX(K)25 9.5CuTFIELD PIPINGFIELD PIPING(6.4CuT)REFRIGERANT FLOWINDOOR UNIT7.9CuTCR

Page 255 - 244 Service Diagnosis

SiE18-201 Wiring DiagramsAppendix 3172. Wiring Diagrams2.1 Outdoor UnitsRMX140JVMB, RMX140JZVMBNACPHPSPMLED2~PCB1~ACNM1CC900~C1RLH1P~L900~CT900~FG1~F1

Page 256

Wiring Diagrams SiE18-201318 Appendix2.2 BP UnitsBPMK928B42BPMK928B4312TO INDOOR UNITSPCB :PRINTED CIRCUIT BOARDFU1~3 :FUSEH1P~H6P:PILOT LAMPR1T~R4T :

Page 257 - 3.3.32 System Malfunction

Specifications SiE18-20122 Specifications Floor Standing Type★ Refer to Engineering Data Book. 2.5kW Class · 3.5kW Class50Hz 230VModelFVX25KZV1B FVX

Page 258 - Service Diagnosis 247

SiE18-201 Wiring DiagramsAppendix 3192.3 Indoor Units2.3.1 Cooling OnlyFHYC35 / 45 / 60 / 71B7V1

Page 259 - 3.3.34 Faulty Fin Thermistor

Wiring Diagrams SiE18-201320 AppendixFHYB35 / 45 / 60 / 71FK7V1

Page 260 - 3.4 How to Check

SiE18-201 Wiring DiagramsAppendix 3212.3.2 Heat PumpFTX25 / 35JAV1NB, FTXD25 / 35KZV1BFTXD50 / 60 / 71JV1BNOTEADDRESS JUMPER IS MARKED "JA"O

Page 261 - Check No.4

Wiring Diagrams SiE18-201322 AppendixCDX25 / 35 / 50 / 60HAV1NB, CDX25 / 35 / 50 / 60JV1NBFLX25 / 35HV1NBRECEIVERSIGNALLEDPCB2H1PCONTROLLERLEDS1WH2PWI

Page 262 - In the case of RMX140JVMC

SiE18-201 Wiring DiagramsAppendix 323FLX50 / 60JV1BFVX25 / 35KZV1BSIGNALRECEIVERLEDH1PPCB4PCB3CONTROLLERLEDH2PS1WWIRELESSREMOTELEDH3PR1TS31t˚S25S27S24

Page 263 - (U, V, W, N)

Wiring Diagrams SiE18-201324 Appendix

Page 264 - Output Voltage

SiE18-201Index iIndexSymbols* ...186, 187, 188, 189Numerics3-Minutes Standby Function ...

Page 265 - (R25=20kΩ, B=3950)

SiE18-201ii IndexFC ...218Field SettingWired Remote Controller ...

Page 266 - Check No.9

SiE18-201Index iiiOutline of System Control ...63Overvoltage, Low Voltage ...239P

Page 267 - Check No.12

SiE18-201iv Index

Page 268 - Check No.14

SiE18-201Printed Circuit Board Connector Wiring Diagram and Name 23Part 3Printed Circuit BoardConnector Wiring DiagramandName1. Printed Circuit Board

Page 269

SiE18-201Drawings & Flow Charts vDrawings & Flow ChartsNumerics1-Room Operation — Indoor Unit Large Capacity (Cooling) ...

Page 270 - 4. BP Unit Trouble Diagnosis

SiE18-201vi Drawings & Flow ChartsPrinted Circuit Board (4) (Signal Receiver PCB) ...36Freeze Prevention Control ...

Page 271 - 260 Service Diagnosis

SiE18-201Drawings & Flow Charts viiPiping DiagramsBPMK928B42 ...311BPMK928B43 ...

Page 272 - Removal Procedure

SiE18-201viii Drawings & Flow Charts

Page 273 - 1. For BPMK928B42 · 43

Daikin Europe N.V. is participating in the EUROVENT Certification Programme. Products are as listed in the EUROVENT Directory of Certified Products. I

Page 274

Printed Circuit Board Connector Wiring Diagram and Name SiE18-20124 Printed Circuit Board Connector Wiring Diagram and Name1. Printed Circuit Board Co

Page 275

SiE18-201 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board Connector Wiring Diagram and Name 251.2 Outdoor Unit RMX140JVMB

Page 276

Printed Circuit Board Connector Wiring Diagram and Name SiE18-20126 Printed Circuit Board Connector Wiring Diagram and NameOther DesignationsPrinted C

Page 277

SiE18-201 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board Connector Wiring Diagram and Name 27Printed Circuit Board (2)(F

Page 278 - Step Procedure Points

Printed Circuit Board Connector Wiring Diagram and Name SiE18-20128 Printed Circuit Board Connector Wiring Diagram and Name1.3 FTX25 / 35J Series, FTX

Page 279 - 1.4 Removal of Thermistor

SiE18-201 Table of Contents iii 3.7 Oil Return Operation... 743.8 Defrost

Page 280 - Removal Procedure 269

SiE18-201 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board Connector Wiring Diagram and Name 29Printed Circuit Board (1)~(

Page 281 - 2. Outdoor Unit

Printed Circuit Board Connector Wiring Diagram and Name SiE18-20130 Printed Circuit Board Connector Wiring Diagram and Name1.4 FTXD50~71JV SeriesHeat

Page 282

SiE18-201 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board Connector Wiring Diagram and Name 31Printed Circuit Board (2)(P

Page 283

Printed Circuit Board Connector Wiring Diagram and Name SiE18-20132 Printed Circuit Board Connector Wiring Diagram and Name1.5 CDX25~60HAV Series, CDX

Page 284 - Connectors

SiE18-201 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board Connector Wiring Diagram and Name 33Printed Circuit Board (1)~(

Page 285 - Filter PCB

Printed Circuit Board Connector Wiring Diagram and Name SiE18-20134 Printed Circuit Board Connector Wiring Diagram and Name1.6 FLX25~60HV Series, FLX5

Page 286

SiE18-201 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board Connector Wiring Diagram and Name 35Printed Circuit Board (1)(C

Page 287

Printed Circuit Board Connector Wiring Diagram and Name SiE18-20136 Printed Circuit Board Connector Wiring Diagram and NamePrinted Circuit Board (3)(D

Page 288

SiE18-201Main Functions 37Part 4Main FunctionsIndoor Unit1. Main Functions...

Page 289 - 278 Removal Procedure

Main Functions SiE18-20138 Main Functions1. Main Functions1.1 Main Functions in Split Type1.1.1 Wide Angle Flaps, Louvers and Auto-SwingFor FTX25/35J

Page 290

SiE18-201 iv Table of Contents 1.12 Equalizing Control (Heating)... 1371.13 Oil Return O

Page 291

SiE18-201 Main FunctionsMain Functions 391.1.2 Fan Speed Control for Indoor UnitsFor FTX25/35J SeriesControl ModeThe airflow rate can be automatically

Page 292 - 2.4 Removal of Thermistor

Main Functions SiE18-20140 Main Functions1.1.5 Washable GrilleWashable grille is for FTK(X)25/35 JNote: Refer to P97 in Si12-001 for FTK25/35 J Series

Page 293 - Putty for check valve

SiE18-201 Main FunctionsMain Functions 411.1.10 Automatic Operation (Heat Pump Only)Automatic Cooling/Heating FunctionWhen the AUTO mode is selected w

Page 294 - Removal Procedure 283

Main Functions SiE18-20142 Main Functions1.1.11 Night Set ModeWhen the OFF Timer is set, the New Night Set Circuit automatically activates.The Night S

Page 295

SiE18-201 Main FunctionsMain Functions 431.1.15 Intelligent EyeFor FTX25/35 JSeries OnlyOutlineThe function that detects existence of humans in the ai

Page 296

Main Functions SiE18-20144 Main Functions Since the set temperature is shifted by 2˚C higher for 40 minutes, compressor speed becomes low and can rea

Page 297 - 2.7 Removal of Compressor

SiE18-201 Main FunctionsMain Functions 451.1.17 Program Dry OperationBy the function of the microcomputer, program dry operation reduces the humidity

Page 298 - Lock nut

Main Functions SiE18-20146 Main Functions1.1.18 Cooling Monitoring FunctionMonitoring function is activated while cooling and program dry operation ar

Page 299 - 2.8 Removal of 4-way Valve

SiE18-201 Main FunctionsMain Functions 471.1.19 Freeze Protection FunctionWhen the indoor heat exchanger temperature falls below “A”˚C in cooling or p

Page 300

Main Functions SiE18-20148 Main Functions1.1.23 Air Flow Automatic (Auto Fan Speed)In cooling operation, if automatic airflow has been selected, the w

Page 301 - 290 Removal Procedure

SiE18-201 Table of Contents v Part 10 Removal Procedure...261 1. For BPMK928B42 · 43 ...

Page 302

SiE18-201 Main FunctionsMain Functions 491.1.25 Emergency Operation Function (ON/OFF Switch)The unit can be turned ON only by pressing ON/OFF operatio

Page 303 - 3. Indoor Unit

Main Functions SiE18-20150 Main Functions1.1.27 Filter Check Indicator The filter check indicator located at the center of the unit will indicate the

Page 304 - Cautions before Operation

SiE18-201 Main FunctionsMain Functions 511.2 SkyAirThermostat ControlExisting cooling/heating preset temperature range has been changed.Draft Avoidanc

Page 305 - 1. Installation

Main Functions SiE18-20152 Main FunctionsDraft Avoidance Control 2When hot start is cancelled or when cold air prevention control is finished, if the

Page 306 - Caution Before Operation 295

SiE18-201 Main FunctionsMain Functions 531.3 Cautions when SkyAir [Auto] [FAN] are used1.3.1 Heat Pump ModelThe Corresponding ModelsFHYB35 / 45 / 60 /

Page 307 - INSTALLATION

Main Functions SiE18-20154 Main Functions

Page 308 - INSTALLATION OF THE MAIN UNIT

SiE18-201Main Functions 55Part 5Main FunctionsOutdoorUnit / BP Unit1. Refrigerant System and Function of Functional Parts of Outdoor Unit .571.1 Refr

Page 309 - 2. Wiring

SiE18-20156 Main Functions3.35 Inter-BP Units Gas Pipe Isothermal Control... 1183.36 BP Unit Motorized Valve Cont

Page 310 - 1, 2, and 3 all match

SiE18-201 Refrigerant System and Function of Functional Parts of Outdoor UnitMain Functions 571. Refrigerant System and Function of Functional Parts o

Page 311 - CONNECTING THE WIRING

Refrigerant System and Function of Functional Parts of Outdoor Unit SiE18-20158 Main Functions1.2 Major Functional Parts Compressor : JT100F-VDThe ap

Page 312

SiE18-201 vi Table of Contents

Page 313 - 302 Caution Before Operation

SiE18-201 Refrigerant System and Function of Functional Parts of Outdoor UnitMain Functions 59 EVT : Motorized valve in non-operating room BP unitIn

Page 314 - Caution Before Operation 303

Refrigerant System and Function of Functional Parts of Outdoor Unit SiE18-20160 Main Functions1.3 Protective Devices, Thermistors, SensorsA HPSWhen th

Page 315 - 3. Others

SiE18-201 Protection DeviceMain Functions 612. Protection Device2.1 Outdoor UnitRMX140JVMM1C Compressor JT100F-VD 3.3kW ° 1 ScrollJ1HC Crankcase Heate

Page 316

Protection Device SiE18-20162 Main Functions2.2 BP UnitBPMK928B42, BPMK928B43FU1 ~ 4 FUSE (3EB82010-1) 250V 3.15AY1E(EVH)ElectronicExpansion ValveMa

Page 317 - 306 Caution Before Operation

SiE18-201 System controlMain Functions 633. System control3.1 Outline of System ControlYESYESYESNONONOBP unitBP unitEVGEVLEVGEVLBP unitBP unitEVGEVG(M

Page 318 - ADDRESS SWITCH

System control SiE18-20164 Main Functions3.2 Mode ConfigurationAir Conditioner Control ModeAir conditioner control modeDetermination of Normal Operati

Page 319

SiE18-201 System controlMain Functions 653.3 Standby Control at Power ONPurpose of the FunctionTo initialize the motorized valve at power ON, to deter

Page 320 - Appendix

System control SiE18-20166 Main Functions3.4 Cooling / Heating Standby Operation at StartupPurpose of the FunctionTo prepare for the next startup afte

Page 321 - 1. Piping Diagrams

SiE18-201 System controlMain Functions 673.5 Equalizing ControlPurpose of the FunctionTo provide equalizing control after a standby operation in order

Page 322

System control SiE18-20168 Main FunctionsEqualizing Control in Heating4-way valve(Delay timer for OFF)Command frequencyOutdoor unit upper fanOutdoor u

Page 323 - 1.3 Indoor Units

SiE18-201 Introduction vii 1. Introduction 1.1 Safety Cautions Cautions and Warnings Be sure to read the following safety cautions before conducting

Page 324 - FLX25 / 35HV1NB

SiE18-201 System controlMain Functions 693.6 Determination of Initial Frequency3.6.1 Determination of Operation FrequencyPurpose of the FunctionTo con

Page 325 - Field Piping φB cut

System control SiE18-20170 Main Functions3.6.2 BP Unit Command Conversion1. ∆D (room temperature − temperature setting) signals from BP units are conv

Page 326 - FTXD25 / 35KZV1B

SiE18-201 System controlMain Functions 713.6.3 Determination of Initial FrequencyInitial frequency setting (determination of initial operating frequen

Page 327 - FVX25 / 35KZV1B

System control SiE18-20172 Main FunctionsDetermination of initial frequency for coolingInitial frequency FSR is determined based on the correction of

Page 328 - 2. Wiring Diagrams

SiE18-201 System controlMain Functions 73Determination of initial frequency for heatingInitial frequency FSR is determined based on the correction of

Page 329 - 2.2 BP Units

System control SiE18-20174 Main Functions3.7 Oil Return OperationPurpose of the FunctionTo collect refrigerating machine oil that adheres on the inter

Page 330 - 2.3 Indoor Units

SiE18-201 System controlMain Functions 75Oil recovery operation in heating modeTOW1(150min)Cumulative heating timeCompressor operation frequencyCompre

Page 331 - FHYB35 / 45 / 60 / 71FK7V1

System control SiE18-20176 Main Functions3.8 Defrost OperationOutline During heating operation, the outdoor heat exchanger intermediate temperature of

Page 332 - FTXD50 / 60 / 71JV1B

SiE18-201 System controlMain Functions 773.9 Pre-Equalization Standby OperationOutline In local air conditioner control mode and frequency fix mode, t

Page 333

System control SiE18-20178 Main Functions3.10 Equalizing ControlOutline This function provides equalizing control after a standby operation in order t

Page 334 - FLX50 / 60JV1B

Introduction SiE18-201 viii 1.1.2 Cautions Regarding Products after Repair Caution Do not repair the electrical components with wet hands.Working on

Page 335 - 324 Appendix

SiE18-201 System controlMain Functions 79Equalizing control in heatingStandbyoperation4-way valve(OFF delay timer)CommandfrequencyOutdoor unitlower fa

Page 336

System control SiE18-20180 Main Functions3.11 Capacity Control3.11.1 Outdoor Unit Motorized Valve Low Pressure (Cooling Capacity) ControlOutline This

Page 337

SiE18-201 System controlMain Functions 813.11.2 Outdoor Unit Motorized Valve High Pressure (Heating Capacity) ControlOutline This function opens the g

Page 338 - Index iii

System control SiE18-20182 Main Functions3.12 Peak Cut ControlOutline Based on the indoor heat exchanger intermediate temperature signal sent from the

Page 339

SiE18-201 System controlMain Functions 833.13 Freeze-Up PreventionOutline According to the freeze prevention status sent from the BP unit, the compres

Page 340 - Drawings & Flow Charts

System control SiE18-20184 Main Functions3.14 Gas Shortage MalfunctionOutline A gas shortage malfunction is detected by using electric current and by

Page 341

SiE18-201 System controlMain Functions 853.15 Discharge Pipe ControlOutline With the internal compressor temperature used as a substitute of the disch

Page 342

System control SiE18-20186 Main Functions3.16 Input Current Control3.16.1 Input Current Control IOutline The input current is detected by CT during co

Page 343

SiE18-201 System controlMain Functions 87Details The input current is used to control the upper limit of the operating frequency in order to maintain

Page 344 - B-8400 Ostend - Belgium

System control SiE18-20188 Main Functions3.16.2 Input Current Control II (High Pressure Control)Outline Based on the input current and input voltage,

Comments to this Manuals

No comments