Method of Field Set SiE18-201
168 Operating Test
Wireless Setting (Address and MAIN/SUB Setting)
Explanation
If several wireless remote controller units are used together in the same room (including the
case where both group control and individual remote controller control are used together), be
sure to set the addresses for the receiver and wireless remote controller. (For group control, see
the attached installation manual for the indoor unit.) If using together with a wired remote
controller, you have to change the main/sub setting or the receiver.
Setting the
Receiver
Through the small opening on the back of the receiver, set the wireless address switch (SS2) on
the printed circuit board according to the table below.
When using both a wired and a wireless remote controller for 1 indoor unit, the wired controller
should be set to MAIN. Therefore, set the MAIN/SUB switch (SS1) of the receiver to SUB.
After completing setting, seal off the opening of the address switch and the MAIN/SUB switch
with the attached sealing pad.
Unit No. No.1 No.2 No.3
Wireless Address
Switch (SS2)
MAIN SUB
MAIN/SUB Switch
(SS1)
Sealing pad
Small
opening
Receiver
(SL004)