Daikin J Series Service Manual Page 254

  • Download
  • Add to my manuals
  • Print
  • Page
    / 344
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 253
SiE18-201 Troubleshooting - Outdoor Unit Related
Service Diagnosis 243
3.3.30 Transmission Error of DC Fan
Outdoor Unit
Indication
U7
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When transmission error with DC fan microcomputer continued for 60 seconds
Supposed
Causes
Incorrect connectors connection
DC fan microcomputer malfunction
Outside causes (noise, etc.)
Malfunction of control PC board receiving circuit
Troubleshooting
Could be outside causes
including noise, etc.
Correct the connection to
restart.
Replace fan PC board.
Is the
error re-generated when
turning the power supply
on again?
(MF050)
YES
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Are DC fan
PC board and control
PC board correctly
connected?
NO
YES
Page view 253
1 2 ... 249 250 251 252 253 254 255 256 257 258 259 ... 343 344

Comments to this Manuals

No comments