For BPMK928B42 · 43 SiE18-201
266 Removal Procedure
4. Dismounting the
motorized valve
Before taking this
procedure, make sure
there is no refrigerant gas
left in the refrigerant
pipes.
Caution
Be careful not to get yourself
burnt with the motorized valve,
pipes and other parts that are
heated by the gas welding rod
When reassembling, place
the thermal insulators back
into position. Using finishing
tape, be sure to join together
the cut-off parts.
1
Cut off the thermal
insulator.
2
Remove the tape and
open the thermal
insulator.
3
Be careful not to allow
flames of a gas welding
rod to affect the parts
around the motorized
valve. To do this, wrap
all the thermal
insulators with water-
wet cloths and place
welding protective
sheets or iron plates
around. Place wet-
water cloth over the top
of the product too.
Step Procedure Points