SiE18-201 Main Functions
Main Functions 39
1.1.2 Fan Speed Control for Indoor Units
For FTX25/35J
Series
Control Mode
The airflow rate can be automatically controlled depending on the difference between the set
temperature and the room temperature. This is done through phase control and Hall IC control.
For more information about Hall IC, refer to ‘Hall IC check (A6)’ on page 258.
Phase Steps Phase control and fan speed control contains 8 steps: LLL, LL, L, ML, M, HM, H and HH.
= Within this range the airflow rate is automatically controlled when the AIRFLOW
ADJUSTING button is set to AUTOMATIC
Note: 1. During powerful operation, fan operate H tap + 50 - 70 rpm.
2. Fan stops during defrost operation.
Automatic Air
Flow Control for
Heating
The following drawing explains the principle for fan speed control for heating:
Note: When there is no operation and the night set mode turns on, the step is low. Refer to “Night set
mode” on page 42.
Automatic Air
Flow Control for
Cooling
The following drawing explains the principle of fan speed control for cooling:
1.1.3 Signal Receiving Sign
When the indoor unit receives a signal from the remote controller, the unit emits a signal
receiving sound.
1.1.4 Air Purifying Filter
For FTX25/35 J
Series
The air purifying filter (electrostatic filter) catches pollen or smoke of cigarette as small as 0.01
micron through electro static charging. An activated carbon deodorizing filter in a net shape is
also mounted to absorb and minimize fine odor particles.
Step Cooling Heating Dry mode
LLL (Heating thermostat
OFF)
H type : 500 - 860 rpm
(During powerful operation :
850 - 910 rpm)
J type : 800 - 980 rpm
(During powerful operation :
1050 rpm)
LL (Cooling thermostat
OFF)
L
ML
M
MH
H
HH (Powerful)
(RL010) (RL010)
-1.5
-1.5
˚C
-0.5
-0.5
˚C
-1
-1
˚C
-2
-2
˚C
L
ML
M
Thermostat
setting
temperature
Phase control
Temperature difference between
ambient and set temperature
fan speed
(RL012)
+1.5
+1.5
˚C
+0.5
+0.5
˚C
+2
+2
˚C
+1
+1
˚C
M
ML
L
fan speed
Temperature difference between
ambient and set temperature
Phase control
Thermostat
setting
temperature
(RL013)