SiE18-201 Operating Test
Operating Test 161
1.2 Test Operation Switch
TEST OPERATION SWITCH [SW7]
Press the FORCED OPERATION SWITCH [SW7]
Aftrer sellecting the COOL/HEAT SWITCH [SW3]
<CAUTIONS>
1) Test operation stops automatically in about 60 minutes .
2) Cooling test operation cannot be performed if the outside air temperature is –5˚C or lower .
3) Operate SkyAir indoor unit in the same mode.
[TO CONTINUE TEST OPERATION]
Press the TEST SW [SW7] again.
[TO RESET TEST OPERATION]
Press the TEST SW [SW7], wait at least 3 seconds and press the TEST SW again.
Digital display:
""
Blinking
(Q0001)