System control SiE18-201
94 Main Functions
3.22 PI Control
Outline Based on the D signal, MAXα of the command frequency is monitored every 20 seconds, and
PI control is provided accordingly. (Coefficient of PI control varies for each S value.)
P Control At every sampling time TFSMP, the maximum value (MAXα) of α value is calculated, and if the
result differs from the previous value, the frequency is changed according to the amount of
fluctuation.
When the previous MAXα is MAXα1 and the newest MAXα is MAXα0, the upper-limit value of
MAXα is
MAX_ALFA_MX(9).
Operating frequency operating amount F: F = KP ° (MAXα0 - MAXα1)
P control is prohibited under the following conditions
(Equation (A))
MAX_ALFA_P1(3) MAXα0 MAX_ALFA_P2(5)
MAX_ALFA_P1(3) MAXα1 MAX_ALFA_P2(5)
P control is prohibited under left condition.
I Control When the D signal does not change for the specified time, the frequency is increased or
decreased according to the MAXα value to set the MAXα value to the specified level.
When MAXα value is small Frequency is decreased
When MAXα value is large Frequency is increased
When MAXα at TFSMP(20) timer time-over is MAXα0:
If MAXα0 MAX_ALFA_12(6)
When frequency does not change for TFSMP ° M(120 sec)
Operating frequency operating amount F is set to F = KI ° (MAXα0 - MAX_ALFA_MK(3))
If MAXα0 MAX_ALFA_11(2)
Operating frequency is decreased at every TFSMP(20 sec)
Operating frequency operating amount F is set to F = -KI ° BI(1)
I control is prohibited when MAX_ALFA_11(2) < MAXα0 < MAX_ALFA_12(6)