SiE18-201 Main Functions
Main Functions 51
1.2 SkyAir
Thermostat
Control
Existing cooling/heating preset temperature range has been changed.
Draft Avoidance
Control 1
Draft is circumvented by delaying transfer of the flap to the Po0 (horizontal) position for a certain
amount of time when defrosting and in the heating mode with the thermostat OFF.
16 17 18 19 20 21 22 23 24 25
25
Initial setting
25
25
25
25
25
H
M
L
26 27 28 29 30 31 32 33 34
(19) (21) (22) (23) (25)
Display
CoolingHeating
Heating
Cooling
Cool/heat
selector
Cool/Heat Automatic
Display
Display
Thermostat ON/OFF
SettingSetting
Wireless Wired
‹When the display is "25" or "H"›
-2deg
-1deg
+2deg
+1deg
(SL017)
Automatic heating
Automatic cooling
Thermostat OFF
Thermostat OFF
Thermostat ON
Thermostat ON
When thermostat is OFF
When the flap begins to
move there is possibility of
feeling a draft during the
time it takes for the fan to
reach LL because of its
inertia.
Flap begins to be driven from
this point in time.
Setting
Setting
On
Off
FAN
LL
Po0
Flap
Comp
T sec.
T: 5 sec (FH(Y)C~K)
T: 20 sec (Other models)
(SL018)
When the flap begins to
move there is possibility of
feeling a draft during the
time it takes for the fan to
reach LL because of its
inertia
Flap begins to be driven from
this point in time.
(SL019)
T sec.
T: 5 sec (FH(Y)C~K)
When defrosting
Setting
OFF
FAN
Flap
Defrosting
IN
OUT
Po0
Setting
T: 20 sec (Other models)
Page view 61