Specifications SiE18-201
16 Specifications
1.2 BP Units
Note:
1. BP or Indoor Unit Max. Height - BP or Indoor Unit Min. Height → Max. 15m.
Set up BP and IU in 15m.
2. The piping connection must be cut so as to suit the piping sizes of the indoor unit which will be connected.
The same sizes should be used for the piping on the outdoor unit.
50Hz 220-240V / 60Hz 220-230V
Model BPMK928B42 BPMK928B43
Connectable Indoor Units 1~2 Units 1~3 Units
Capacity
Cooling kW — —
Heating kW — —
Casing Color Paintingless
Power Consumption W 10 10
Running Current A 0.05 0.05
Refrigerant
Type —
Charge kg —
Dimensions (H×W×D) mm 223×400×272
Package Dimensions mm 651×342×281
Machine Weight kg 7 8
Gross Weight kg 10 11
Number of Wiring Connections 4 for Interunit Wiring
Piping
Connection
(Brazing)
Liquid mm Main : φ9.5×1/ Branch : φ6.4×2 Main : φ9.5×1/ Branch : φ6.4×3
Gas mm Main : φ19.1×1 / Branch : φ15.9×2 Main : φ19.1×1 / Branch : φ15.9×3
Drain mm Drain Processingless
Heat Insulation Both Liquid and Gas Pipes
Max. Piping Length m —
Amount of Additional Charge g/m —
Max. Height Difference m —
Max. Combination kW 18.9 18.9
Min. Combination kW 2.5 2.5
Accessories
Installation Manual pc. 1
L Shape Reducer pc.
For Main (Gas) 1
For Branch
Gas 3 (φ15.9 / φ12.7 / φ9.5)
Liquid 1 (φ9.5)
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414