Outdoor Unit SiE18-201
290 Removal Procedure
7
Cut off the
compressor's
discharge pipe (at point
L) with the pipe cutter.
8
Disconnect the 4-way
valve assembly.
In reconnecting the 4-way
valve assembly, braze the
cut-off point together with a
copper tube union (Local
supply).
It may be difficult to
disconnect the
pipes (at points A
and B) of the
accumulator
(discussed in Step
(4) above). In such
case, use the pipe
cutter. When
reconnecting the 4-
way valve
assembly, braze the
cut-off point
together with a
copper tube union.
Step Procedure Points
Point L
Cut-off
point
(M1221)
(M1222)