SiE18-201 Troubleshooting - Split Type Indoor Unit
Service Diagnosis 189
1.5.8 Faulty Power Supply or Indoor Unit PCB (For FTK(X)50/60H,
CDK(X)25~60H)
Remote
Controller
Display
or U4
Indoor Unit LED
Display
A 3 B
Note: No LED Display on FTK(X)25/35J Series.
Method of
Malfunction
Detection
The proper program operation of the microcomputer is checked by the program.
Malfunction
Decision
Conditions
When the microcomputer program does not function properly.
Supposed
Causes
Display disabled by fault power supply.
Microcomputer program is in abnormal condition due to an external factor.
Noise.
Momentary voltage drop.
Momentary power failure, etc.
Faulty indoor unit PCBs (1) and (2).