Daikin J Series Service Manual Page 191

  • Download
  • Add to my manuals
  • Print
  • Page
    / 344
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 190
Troubleshooting - Split Type Indoor Unit SiE18-201
180 Service Diagnosis
1.4 Troubleshooting
1.4.1 Indoor Units
FTX25/35 J Series - : Not used for troubleshooting
: Varies depending on the cases.
CDX25~60H
Series
4: ON, 1: OFF, 5: Blinks
Green: Flashes when in normal condition
Red: OFF in normal condition
- : Not used for troubleshooting
: Varies depending on the cases.
Indication on the
remote
controller
Description of the Fault Details of fault
(Refer to the
indicated
page.)
00 or
Indoor unit in normal condition (Conduct a diagnosis of the
outdoor unit.)
A1
Inverter unit - Faulty indoor unit PCB 181
A5
Operation halt due to the freeze protection function or high
pressure control (heat pump model only)
182
A6
Faulty fan motor (AC motor stop) AC motor 184
C4
Heat exchanger temperature thermistor or related abnormality 185
C9
Suction thermistor or related abnormality 185
CA
Discharge thermistor or related abnormality 185
Faulty indoor unit PCB
186
187
or U4
Faulty power supply or indoor unit PCB 188
U4
Signal transmission error (between indoor and outdoor units) 192
Indoor Unit LED
Indication
Indication on the
remote
controller
Description of the Fault Details of fault
(Refer to the
indicated
page.)
Green
AB
5500 or
Indoor unit in normal condition (Conduct a diagnosis of the
outdoor unit.)
55
55A5
Operation halt due to the freeze protection function or high
pressure control (heat pump model only)
182
55
55A6
Faulty fan motor (AC motor stop) AC motor 184
55
55C4 or C5
Heat exchanger temperature thermistor or related abnormality 185
55
55C9
Suction thermistor or related abnormality 185
55CA
Discharge thermistor or related abnormality 185
4
Faulty indoor unit PCB 186
54
187
1
or U4
Faulty power supply or indoor unit PCB 188, 189
190, 191
51U4
Signal transmission error (between indoor and outdoor units) 192
51U5
Signal transmission error (between indoor unit and remote
controller)
193
Page view 190
1 2 ... 186 187 188 189 190 191 192 193 194 195 196 ... 343 344