SiE18-201 Troubleshooting - Outdoor Unit Related
Service Diagnosis 249
3.4 How to Check
3.4.1 Installation Condition Check
Check No.1
3.4.2 Discharge Pressure Check
Check No.2
Installation condition check
Normal
Change the position of the
air discharge grille or the
installation location.
Change the position of the
air discharge grille or the
installation location.
Clean the heat exchanger.
Change the installation
location or direction.
Check the outside air
temperature (temperature
of air taken in by the
outdoor unit).
(The outside air
temperature shall be 43˚C
or lower.)
Check
the allowable
dimensions of the air suction
and discharge
area.
Is
the air flow
blocked by obstacles
or winds blowing in the
opposite direction?
(MF030)
Abnormal
YES
YES
YES
Does
the discharged
air from other outdoor
unit cause an increase of
the suction air
temperature?
NO
NO
NO
Is the heat exchanger
very dirty?
Discharge pressure check
Open the stop valve.
Replace the pipe installed
at the site.
Clean.
Replace the compressor.
(MF031)
YES
YES
YES
NO
NO
NO
At the
heat exchanger and
air filter dirty?
Is the stop valve open?
Is the
connection pipe
deformed?