Daikin J Series Service Manual Page 84

  • Download
  • Add to my manuals
  • Print
  • Page
    / 344
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 83
SiE18-201 System control
Main Functions 73
Determination of initial frequency for heating
Initial frequency FSR is determined based on the correction of outside air temperature (DOA)
and discharge pipe temperature (DO) in accordance with the above matrix.
FSR = KFIDO ° (-5/128 ° (DOA - 15˚C) ° FINI1+FINI1)
3/ KFIDO varies depending on discharge pipe temperature DO
When DO DOFINI (45˚C): KFIDO = KFIDOH (128/128) --- Hot start
When DO < DOFINI (45˚C): KFIDO = KFIDOL (179/128) --- Cold start
Reference Outside Air
Temperature
Hot Start Cold Start
15˚C 128/128 179/128
Outside Air
Temperature
Hot Start Cold Start
-15 217.2% 303.7%
-10 197.7% 276.4%
-5 178.1% 249.1%
0 158.6% 221.8%
5 139.1% 194.5%
10 119.5% 167.2%
15 100.0% 139.8%
20 80.5% 112.5%
25 60.9% 85.2%
Initial HZ multiplication
Hot start
Cold start
-20 -15 -10 -5 0 10 15 20 25
30
Outside
air temperature
0%
50%
100%
150%
200%
250%
300%
(M1010)
Page view 83
1 2 ... 79 80 81 82 83 84 85 86 87 88 89 ... 343 344

Comments to this Manuals

No comments