60 Catalog 602-2
7. The chiller shall be capable of cycling and loading up to three other similar chillers through a local
network and also automatic control of evaporator and condenser pumps (primary and standby), up
to 3 stages of cooling tower fan cycling control and a tower modulating bypass valve or cooling
tower fan variable frequency drives.
8. [OPTIONAL] The factory mounted controller(s) shall support operation on a BACnet®,
Modbus® or LONWORKS® network via one of the data link / physical layers listed below as
specified by the successful Building Automation System (BAS) supplier.
Modbus
BACnet MS/TP master (Clause 9)
BACnet IP, (Annex J)
BACnet ISO 8802-3, (Ethernet)
LonTalk® FTT-10A. The unit controller shall be LONMARK ® certified.
9. The information communicated between the BAS and the factory mounted unit controllers shall
include the reading and writing of data to allow unit monitoring, control and alarm notification as
specified in the unit sequence of operation and the unit points list.
10. For chillers communicating over a LONMARK network, the corresponding LONMARK eXternal
Interface File (XIF) shall be provided with the chiller submittal data.
11. All communication from the chiller unit controller as specified in the points list shall be via
standard BACnet objects. Proprietary BACnet objects shall not be allowed. BACnet
communications shall conform to the BACnet protocol (ANSI/ASHRAE135-2001). A BACnet
Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit
submittal.
12. The factory supplied VFD and controls should include the following:
High short circuit panel rating of [35 kA (standard)] OR [65kA at 460V (optional)] with a
field-supplied matching disconnect switch
Phase loss protection
Under/over voltage protection
[OPTIONAL] Ground Fault Protection to reduce the arcing ground fault damage from line-to-
ground fault currents less than those required for conductor protection
[OPTIONAL] EMI filters to reduce radio frequency interference
13. Energy saving software logic shall at a minimum offer the following
User programmable compressor soft loading
Chilled water reset
Demand limit control
Staging options lead lag between multiple compressors on a single chiller or up to two other
similar chillers.
Plotting of historic trends for optimizing efficiency
2.5. OPTIONAL ITEMS
The following optional items shall be furnished:
1. [Open] OR [Closed] export crate
2. Pumpout unit, with or without storage vessel
3. Refrigerant monitor
4. OSHPD Certification: The chiller shall be OSHPD Pre-Approved per OSP–0116-10 and be so labeled. The
chiller shall meet a minimum seismic design spectral response acceleration of 1.60 S
DS
. The chiller must
be mounted to a rigid base and may use neoprene waffle vibration pads.