28 Catalog 602-2
Physical Data
Evaporator
Refrigerant-side design pressure is 200 psi
(1379 kPa). Water-side is 150 psi (1034 kPa).
Approximate total square footage of insulation
surface required for individual packaged chillers is
tabulated by evaporator code and can be found
below. The suction elbow and compressor also
require insulation.
Table 12, Evaporator Physical Data
WMC
Model
Evaporator
Model
Tube
Length
Unit Refrigerant
Charge
lb. (kg)
Evaporator
Water
Volume, gal (L)
Insulation
Area
sq. ft. (m
2
)
Number of
Relief
Valves
145S 145D
E2209 9 ft. 550 (250) 38 (145) 66 (6.1) 1
150D
E2212 12 ft. 800 (363) 45 (170) 90 (8.3) 1
250D
E2609 9 ft. 600 (272) 61 (231) 76 (7.1) 1
290D
E2612 12 ft. 1100 (500) 72 (273) 102 (9.4) 1
400D
E3012 12 ft. 1240 (562) 88 (336) 114 (11) 1
Notes:
1. Refrigerant charge is approximate since the actual charge will depend on other variables. Actual charge will be shown on the
unit nameplate and is tabulated above.
2. Water capacity is based on standard tube configuration and standard dished heads.
Condenser
With positive pressure systems, the pressure
variance with temperature is always predictable
and the vessel design and pressure relief
protection are based upon pure refrigerant
characteristics. R-134a requires ASME vessel
design, inspection and testing and uses spring-
loaded pressure relief valves. When an over-
pressure condition occurs, spring-loaded relief
valves purge only that quantity of refrigerant
required to reduce system pressure to the valve’s
set pressure, and then close.
Refrigerant-side design pressure is 200 psi (1380
kPa). Water-side design is 150 psi (1034 kPa).
Table 13, Condenser Physical Data
WMC
Model
Condenser
Model
Tube
Length
Maximum
Pumpdown
Capacity lb. (kg)
Water
Volume
gal. (L)
Number of
Relief Valves
145S, 145D
C2009 9 ft. 728 (330) 47 (147) 2
150D
C2012 12 ft. 971 (440) 62 (236) 2
250D
C2209 9 ft. 883 (401) 50 (223) 2
290D
C2212 12 ft. 1174 (533) 72 (273) 2
400D
C2612 12 ft. 1676 (760) 111 (419) 2
Notes:
1. Condenser pumpdown capacity based on 90% full at 90F.
2. Water capacity based on standard configuration and standard heads and can be less with lower tube counts.
3. See Relief Valves section for additional information.