Catalog 602-2 59
Piping
Tank
Heater
Cooler
Controls
Valves
3. Manufacturer shall be responsible for covering all costs associated with annual oil and oil filter
changes plus oil analysis as required
D. Vibration Isolation
1. Provide neoprene waffle-type vibration isolators for each corner of the unit.
E. Power Connections
1. Power connection shall be [single point to a factory-mounted disconnect switch] OR [multipoint to
each compressor power panel on two-compressor units].
F. Chiller Control
1. The unit shall have a microprocessor-based control system consisting of a 15-inch VGA touch-
screen operator interface and a unit controller.
2. The touch-screen shall display the unit operating parameters, accept setpoint changes (multi-level
password protected) and be capable of resetting faults and alarms. The following parameters shall
be displayed on the home screen and also as trend curves on the trend screen:
Entering and leaving chilled water temperatures
Entering and leaving condenser water temperatures
Evaporator saturated refrigerant pressure
Condenser saturated refrigerant pressure
Percent of 100% speed (per compressor)
% of rated load amps for entire unit
3. In addition to the trended items above, all other important real-time operating parameters shall
also be shown on the touch-screen. These items shall be displayed on a chiller graphic showing
each component. At a minimum, the following critical areas must be monitored:
Compressor actual speed, maximum speed, percent speed
Liquid line temperature
Chilled water setpoint
Compressor and unit state and input and output digital and analog values
4. A fault history shall be displayed using an easy to decipher, color coded set of messages that are
date and time stamped. Time interval scale shall be user selectable as 20 mins, 2 hours, or 8
hours. The alarm history shall be downloadable from the unit's USB port. An operating and
maintenance manual specific for the unit shall be viewable on the screen.
5. All setpoints shall be viewable and changeable (multi-level password protected) on the touch
screen and include setpoint description and range of set values.
6. Automatic corrective action to reduce unnecessary cycling shall be accomplished through
preemptive control of low evaporator or high discharge pressure conditions to keep the unit
operating through abnormal transient conditions.