14 Catalog 602-2
Table 2, ASHRAE 90.1 Requirements (kW/ton)
Pre 2010 Starting in 2010
Path A Path B
Std. 90.1
Capacity
Range
Full
Load
IPLV
Full
Load-
IPLV
Full
Load-
IPLV
150 Tons 0.703 0.669
0.634 0.596
0.639 0.450
150 Tons
300 Tons
0.634 0.596 0.634 0.596 0.639 0.450
300 Tons
600 Tons
0.576 0.549 0.576 0.549 0.600 0.400
NOTE: Beginning in 2010, the 90.1 efficiency
requirements have been divided into two groups,
designated as Path A and Path B. Path B is a new
category created for units with VFD compressor drives
that by nature have superior part-load efficiencies. WMC
Magnitude chillers, with their built-in VFDs, fall into
Path B.
The Path B IPLV values for 2010 are about 30 percent
less than the 2007 equivalent values. Also beginning in
2010, the minimum efficiency values are formula derived
instead tabular so that they can take flows and
temperatures other than AHRI standard into account.
AHRI Certification
McQuay International has an on-going
commitment to supply chillers that perform as
specified. To this extent, Daikin McQuay
centrifugal chillers are part of the AHRI
Certification Program. On-going performance
verification of chiller capacity and power input
plus AHRI certified computerized selection output
provide the owner with specified performance in
accordance with the latest version of AHRI
Standard 550/590.
All chillers that fall within the scope of the
certification program have an AHRI certification
label at no cost to the owner. Equipment covered
by the AHRI certification program includes all
water-cooled centrifugal and screw water chilling
packages rated up to 2500 tons (8800 kW) at AHRI
standard rating conditions, hermetic or open drive,
with electric driven motor not exceeding 5000
volts, and cooling water (not glycol).
Published certified ratings verified through testing
by AHRI include:
Capacity, tons (kW)
Power, kW/ton (COP)
Pressure drops, ft. of water (kPa)
Integrated Part Load Value (IPLV) or Non-
Standard Part Load Value (NPLV)
The AHRI Standard 550/590 for Centrifugal or
Screw Water-Chilling Packages and associated
manuals define certification and testing procedures
and performance tolerances of all units that fall
within the application rating conditions.
Leaving chilled water temp.: 40F to 48°F (44F
standard)
Entering condenser water temp.: 60F to 95°F
Leaving chilled water temp.: 44°F
Evap. waterside field fouling allowance: 0.0001
Chilled water flow rate: 2.4 gpm/ton
Entering condenser water temp.: 85°F
Condenser waterside field fouling allowance:
0.00025
Condenser water flow rate: 3.0 gpm/ton
IPLV/NPLV Defined
Part load performance can be presented in terms of
Integrated Part Load Value (IPLV), which is based
on AHRI standard rating conditions (listed above),
or Non-Standard Part Load Values (NPLV), which
is based on specified or job site conditions. IPLV
and NPLV are based on the following weighting
equation from AHRI 550/590:
Using kW/ton:
DCBA
IPLVorNPLV
12.0
+
45.0
+
42.0
+
01.0
1
=
Where:
A = kW/ton at 100%
B = kW/ton at 75%
C = kW/ton at 50%
D = kW/ton at 25%
Or, using COP values:
DCBAIPLVorNPLV 12.0+45.0+42.0+01.0=
Where:
A = COP at 100%
B = COP at 75%
C = COP at 50%
D = COP at 25%
Page view 13