Daikin WMC Specifications Page 52

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 51
52 Catalog 602-2
SPECIFICATIONS
Sensitivity: As low as 1 PPM Range: 0 to 1000 PPM Weight: 25 lbs. (11 kg)
Power: 120/240 Volt, 50/60 Hz
Operating Environment: 32F-125F
Size: W=16.5in. D=6.75in. H=15in.
Alarm Trip Points (Percent of Full Scale): Low Alarm=0 to 100, Main Alarm=0 to 100, High Alarm=100
Alarm Outputs: Indicator Light, Alarm Relays, RS232 Computer Interface
OPTIONS and ACCESSORIES
Analog Output, 4-20 ma (RMA-AO) Remote Strobe Light, 120 V (RMA-L)
Remote Horn, 120V (RMA-H) Remote Light and Horn Set (RMA-LH)
Plastic Pick-up Tubing, ¼ inch OD, 250 ft. Reel (RMA-T) Diaphragm Pump (RMA-P) *
Course Replacement Filter (RMA-CF) * 5 Micron Replacement Filter (RMA-F) *
(*) Replacement parts. Original pump and filters are shipped with unit.
SYSTEM DESCRIPTION
Item Description Required
Supplied
with
Unit
Supplied
by
Customer
Optional
Available
from
Daikin
McQuay
Comments
1
16 gauge
3 conductor wire
Yes No Yes No
2
18 or 22 gauge
2 conductor cable
No Yes No
Required for horn,
strobe, or combination
3
2 conductor twisted
pair shielded cable
No Yes No
Required for remote
analog output
4 Remote horn No Yes Yes
5 Remote strobe light No Yes Yes
6
Remote horn and
strobe light set
No Yes Yes
7
1/4 in. x 1/8 in. ID
plastic pick-up tubing
Yes No Yes
Available in 250 foot
reels
8 Course filter Yes Yes
For mounting at the
end of the tubing
Figure 23, Refrigerant Monitor Diagram