58 Catalog 602-2
a minimum of 200 psi. Provide intermediate tube supports at a maximum of 24 inch spacing. The
heads shall be [carbon steel] OR [epoxy-coated steel]. Water connections shall be [grooved
suitable for Victaulic couplings] OR [flanged connections]. The evaporator shall have [dished
heads with valved drain and vent connections] OR [shall be equipped with marine water boxes
with removable covers and vent and drain connections]. The evaporator shall have [right-hand]
OR [left-hand] connections when looking at the unit control panel.
2. The condenser shall have [(0.025 in) OR (0.028 in.) OR (0.035 in.) wall copper] OR [(0.028 in.) or
(0.035 in.) wall 90-10 cupro-nickel] internally and externally enhanced tubes rolled into carbon
steel. Water connections shall be [grooved suitable for Victaulic couplings] OR [flanged]. The
water side shall be designed for a minimum of [150 psig] OR [300 psig]. The refrigerant side shall
be designed for a minimum of 200 psi. Provide intermediate tube supports at a maximum of 24
inch spacing. The condenser shall have [dished heads with valved drain and vent connections] OR
[shall be equipped with marine water boxes with removable covers and vent and drain
connections]. The heads shall be [carbon steel] OR [epoxy-coated steel]. The condenser shall have
[right-hand] OR [left-hand] connections when looking at the unit control panel.
3. Provide sufficient isolation valves and condenser volume to hold the full unit refrigerant charge
the condenser at 90ºF in accordance with ANSIASHRAE 15.A during servicing or provide a
separate pumpout system and storage tank sufficient to hold the charge of the largest unit being
furnished.
4. An electronic expansion valve shall control refrigerant flow to the evaporator. Fixed orifice
devices or float controls with hot gas bypass are not acceptable because of inefficient control at
low load conditions. The liquid line shall have moisture indicating sight glass.
5. Re-seating type spring loaded pressure relief valves according to ASHRAE-15 safety code shall be
furnished. The evaporator shall be provided with single or multiple valves. The condenser shall be
provided with dual relief valves equipped with a transfer valve so one relief valve can be removed
for testing or replacement without loss of refrigerant or removal of refrigerant from the condenser.
Rupture disks are not acceptable. If rupture disks are required on negative pressure units to
prevent air and moisture ingress, then factory mounted spring loaded pressure relief valves shall be
provided in series with the rupture disks to contain the remaining refrigerant in the event of vessel
over-pressurization. The space between the rupture disk and the relief valve shall include a
suitable telltale indicator integrated into the chiller control system to alert the operator that a
potential safety issue exists in the pressure relief system.
6. [OPTIONAL] The evaporator, including water heads, suction line, and any other component or
part of a component subject to condensing moisture shall be insulated with UL recognized [3/4
inch] OR [1 ½ inch] closed cell insulation. All joints and seams shall be carefully sealed to form a
vapor barrier.
7. Provide factory-mounted and wired, thermal-dispersion water flow switches on each vessel to
prevent unit operation with no or low water flow. Paddle and pressure differential type switches
are not acceptable due to high rates of failure and false indications from these types of flow
indicators.
C. Long Term Reliability
1. All compressor/motor designs that require oil to lubricate their respective roller/ball bearing
system must denote exactly how many gallons of oil are required for safe operation. The
manufacturer must then provide the engineer and owner with a real world energy analysis
showing the energy degradation over time due oil contamination of heat transfer surfaces
.
2. Chillers containing oil shall include at no additional charge a 10 year parts and labor warranty
on all oil system components including:
Pumps Starter