30 Catalog 602-2
Electrical Data
General Note: The RLA for use in the following tables is obtained by the selection of a specific unit by Daikin
McQuay. When shipped, a unit will bear the specific RLA, stamped on the nameplate, for the selected operating
conditions.
!
CAUTION
The RLA stamped on the unit may be lower than the minimum shown in the following tables, in which case the
minimum table value must be used for wire sizing.
Table 14, Electrical Acronyms and Notes
ACRONYMS:
DS Disconnect switch
LRA Locked rotor amps
N/A Not available
MCA Minimum circuit ampacity
MOP Maximum overcurrent protection
PB Power block
RLA Rated load amps
NOTES:
1
In all cases, a disconnect switch is supplied for each compressor circuit.
2 RLA and LRA data is for each compressor
3 Wire size per NEC 2008, table 310.16, 75° C, copper
4 MOP size per NEC 2008, section 440.22(a) for air conditioning and refrigeration equip.
WMC 145S, Single Compressor
Table 15, WMC 145S-B, 3/60/460
SINGLE POINT CONNECTION, STANDARD
COMPRESSOR CHILLER
RLA
[Amp]
LRA
[Amp]
QTY
MCA
[Amp]
MOP
[Amp]
DISC.
SWT.
[Amp]
POWER
BLOCK
[Amp]
WIRE
QTY
WIRE
GAUGE
79 to 80 110 1 99 to 100 175 150 3 3 GA
81 to 88 110 1 101 to 110 175 150 3 2 GA
89 to 92 110 1 111 to 115 200 150 3 2 GA
93 to 99 110 1 116 to 123 200 150 3 1 GA
100 110 1 125 225 150 3 1 GA
101 to 104 132 1 126 to 130 225 200 3 1 GA
105 to 111 132 1 131 to 138 225 200 3 1/0
112 to 120 132 1 140 to 150 250 200 3 1/0
121 to 133 154 1 151 to 166 250 225 3 2/0
134 to 140 154 1 167 to 175 300 225 3 2/0
141 to 150 165 1 176 to 187 300 225
N/A
3 3/0