Daikin WMC Specifications Page 15

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 14
Catalog 602-2 15
Weighting
The percent of annual hours of operation at the
four load points are as follows:
100% Load at 1%
75% Load at 42%
50% Load at 45%
25% Load at 12%
Note that the vast majority of hours are at the operating
range where dual compressor chillers excel.
Tolerances
The AHRI test tolerance, per AHRI Standard
550/590-98, for capacity (tons), power input per
ton (kW/ton), and heat balance is:
%.(.%)
%
Tolerance x FL
DTFLx FL

10 5 0 07
1500
Where:
FL = Full Load
DTFL = Chilled Water Delta-T at Full Load
This formula results in a 5% tolerance on tons
and kW/ton at the 100% load point and AHRI
conditions.