SECTION 15XXX
MAGNETIC BEARING CENTRIFUGAL CHILLERS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes design, performance criteria, refrigerants, controls, and installation requirements for
water-cooled centrifugal chillers.
1.2 REFERENCES
A. Comply with the following codes and standards:
AHRI 550/590
AHRI 575
NEC
ANSI/ASHRAE 15
OSHA as adopted by the State
ETL
ASME Section VIII
1.3 SUBMITTALS
A. Submittals shall include the following:
1. Dimensioned plan and elevation view, including required clearances, and location of all field piping
and electrical connections.
2. Summaries of all auxiliary utility requirements such as: electricity, water, air, etc. Summary shall
indicate quality and quantity of each required utility.
3. Diagram of control system indicating points for field interface and field connection. Diagram shall
fully depict field and factory wiring.
4. Manufacturer's certified performance data at full load plus IPLV or NPLV.
5. Installation and Operating Manuals.
1.4 QUALITY ASSURANCE
A. Regulatory Requirements: Comply with the codes and standards in Section 1.2.
B. Chiller manufacturer plant shall be ISO Certified.
C. The chiller shall be tested to job conditions at the manufacturer's plant.
1.5 DELIVERY AND HANDLING
A. Chillers shall be delivered to the job site completely assembled and charged with refrigerant R134a and be
shipped on skids with a weather resistant cover.
-- OR --
A. (For Type IV Knockdown) The compressor(s) and control and power panel(s) shall be removed at the
factory and shipped on skids. The stripped vessel stack shall be shipped as a single piece. Discharge
piping, liquid line and the compressor cooling lines shall be removed and crated. All associated wiring