Daikin WMC Specifications Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
Catalog 602-2 13
Electronic Expansion Valve
Controlled refrigerant flow over the entire capacity
range saves energy and dollars. Cooling loads and
condenser water temperatures can change
constantly. On Magnitude chillers, a modern
electronic expansion valve meters refrigerant flow
in direct response to the unit controller input,
which looks at unit kW and lift (discharge minus
suction pressure) to set the valve position. The
controller then balances suction superheat and
liquid subcooling to reach the optimum efficiency,
regardless of changing load or condensing
temperatures. In doing so, full utilization of
compressor, evaporator, and condenser efficiency
over the entire operating range is achieved.
Flow Switch
All chiller units must be provided with flow
switches for the evaporator and condenser. Daikin
McQuay furnishes factory-installed and wired,
thermal dispersion-type flow switches as standard
equipment on Magnitude chillers. This eliminates
the expense of field mounting and wiring
conventional paddle or differential pressure
switches.
The flow switches
prevent the unit
from starting
without sufficient
water flow through
the vessels. They
also serve to shut
down the unit in
the event that
water flow is
interrupted to
guard against evaporator freeze-up or excessive
discharge pressure.
Additionally, for a higher margin of protection,
normally open auxiliary contacts in the pump
starters can be wired in series with the flow switches
as shown in the Field Wiring Diagram.
Factory Performance Test
Fast and trouble free startup and operation
.
All Daikin McQuay centrifugal chillers are factory-
tested on AHRI qualified microprocessor-controlled
test stands. The test stand microprocessors interface
with the chiller MicroTech controls, allowing
monitoring of all aspects of the test stand and chiller
operation.
The test procedure starts with dehydration and
evacuation of the refrigerant circuit and charging
with refrigerant. This is followed by a run test at job
conditions of flow and temperature. Compressors
must meet a stringent vibration limit and the entire
unit must pass a moisture limit of 30 ppm.
The testing helps ensure correct operation prior to
shipment and allows factory calibration of chiller
operating controls.
Optional Certified Test
A factory engineer oversees the testing, certifies the
accuracy of the computerized results, and translates
the test data onto an easy-to-read spreadsheet. The
tests are run to AHRI tolerance of capacity and
power. 50 Hertz units are tested using an on-site 50
Hertz generator.
Optional Witness Test
A factory engineer oversees the testing in the
presence of the customer or their designate and
translates the test data onto an easy-to-read
spreadsheet. Tests are run to AHRI tolerances of
capacity and power. 50 Hertz units are tested using
an on-site 50 Hertz generator.
McQuay Factory Service Startup
All Daikin McQuay centrifugal chillers are
commissioned by local McQuay Factory Service
personnel or by authorized McQuay startup
technicians. This procedure helps assure that proper
starting and checkout procedures are employed and
helps speed up the commissioning process.
Part Load Efficiency
According to ASHRAE, chillers usually spend
99% of their operating hours under part load
conditions and most of this time at less than 60%
of design capacity. One compressor of a dual
chiller operates with the full heat transfer surface
of the entire unit. For example, one 75-ton
compressor on a 150-ton dual chiller utilizes 150
tons of evaporator and condenser surface. This
results in very high unit efficiency and also
increases the compressors capacity.
The inclusion of VFDs, as standard, to the dual
compressor chiller can produce astonishing AHRI
Certified IPLVs,
as low as 0.328 kW/ton. Specific
selections can vary from this example.
Compliance with ASHRAE Std. 90.1
With the Magnitude chiller capacity range of 145
to 400 tons, they fall into three ASHRAE Std. 90.1
efficiency groups and revisions.
Page view 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 63 64

Comments to this Manuals

No comments