40 Catalog 602-2
The power line noise emissions associated with
variable frequency and variable speed drives can
cause disturbances in nearby equipment. Typical
disturbances include:
Dimmer and ballast instability
Lighting disturbances such as flashing
Poor radio reception
Poor television reception
Instability of control systems
Flow meter totalizing
Flow metering fluctuation
Computer system failures loss of data
The IEEE 519-1991 Standard
The Institute of Electrical and Electronics
Engineers (IEEE) has developed a standard that
defines acceptable limits of system current and
voltage distortion. A simple form is available from
McQuay International that can be used to perform
a harmonics analysis and to determine compliance
with IEEE 519-1991.
Line reactors, isolation transformers, or phase-
shifting transformers can be required on some
installations.
Radar disruption
Sonar disruption
Thermostat control problems