Daikin WMC Specifications Page 43

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 42
Catalog 602-2 43
determined from the Daikin McQuay selection
program.
We recommend variable flow only in the
evaporator because there is virtually no change in
chiller efficiency compared to constant flow. In
other words, there is no chiller energy penalty and
considerable pumping energy can be saved.
Although variable speed pumping can be done in
the condenser loop, it is usually unwise. The intent
of variable flow is to reduce pump horsepower.
However, reducing condenser water flow increases
the chillers condensing pressure, increasing the
lift that the compressor must overcome which, in
turn, increases the compressors energy use.
Consequently, pump energy savings can be lost
because the chiller operating power is significantly
increased.
Low condenser flow and tube velocities can cause
premature tube fouling and subsequent increased
compressor power consumption. Increased
cleaning and/or chemical use can also result.
Vibration Mounting
The Magnitude chillers are almost vibration-free.
Consequently, floor mounted spring isolators are
not usually required. Rubber mounting pads are
shipped with each unit. It is wise to continue to
use piping flexible connectors to reduce sound
transmitted into the pipe and to allow for
expansion and contraction.
System Water Volume
All chilled water systems need adequate time to
recognize a load change, respond to that load
change and stabilize, without undesirable short
cycling of the compressors or loss of control. In
air conditioning systems, the potential for short
cycling usually exists when the building load falls
below the minimum chiller plant capacity or on
close-coupled systems with very small water
volumes.
Some of the things the designer should consider
when looking at water volume are the minimum
cooling load, the minimum chiller plant capacity
during the low load period and the desired cycle
time for the compressors.
Assuming that there are no sudden load changes
and the chiller plant has reasonable turndown, a
rule of thumb of “gallons of water volume equal
to two to three times the chilled water gpm flow
rate” is often used.
A properly designed storage tank should be
added if the system components do not provide
sufficient water volume.
Pump Control
Operation of the chilled water pump can be to:
1) cycle the pump with the unit
2) operate continuously
3) cycle automatically by a remote source
The cooling tower pump must cycle with the
compressor. The holding coil of the cooling
tower pump motor starter must be rated at 115
volts, 60 Hz, with a maximum volt-amperage
rating of 100. A control relay is required if the
voltage-amperage rating is exceeded. See the
Field Wiring Diagram on page 38 or in the
cover of control panel for proper connections.
All interlock contacts m
ust be rated for no less
than 10 inductive amps. The alarm circuit
provided in the control center utilizes 115-volts
AC. The alarm used must not draw more than
10-volt amperes.
System analysis
Although McQuay International is a proponent
of analyzing the entire system, it is generally
effective to place the chiller in the most
efficient mode because it is a large energy
consumer.
The McQuay Energy Analyzer program is an
excellent tool to investigate the entire system
efficiency, quickly and accurately. It is
especially good at comparing different system
types and operating parameters. Contact you
local Daikin McQuay sales office for assistance
on your particular application.
Page view 42
1 2 ... 38 39 40 41 42 43 44 45 46 47 48 ... 63 64

Comments to this Manuals

No comments