Catalog 602-2 41
Application
Considerations
Location
WMC chillers are intended only for installation in
an indoor or weather protected area consistent with
the NEMA 1 rating on the chiller, controls, and
electrical panels. Equipment room temperature for
operating and standby conditions is 40°F to 122°F
(4.4°C to 50°C).
Optimum Water
Temperatures and Flow
A key to improving energy efficiency for any
chiller is minimizing the compressor pressure lift.
Reducing the lift reduces the compressor work and
its energy consumption per unit of output. The
chiller typically has the largest motor of any
component in a chilled water system.
Higher leaving chilled water
temperatures
Warmer leaving chilled water temperatures will
raise the compressors suction pressure and
decrease the lift, improving efficiency. Using 45F
(7.0C) leaving water instead of 42F (5.5C) will
make a significant improvement.
Evaporator temperature drop
The industry standard has been a 10-degree F (5.5
degree C) temperature drop in the evaporator.
Increasing the drop to 12 or 14 degrees F (6.6 or
7.7 degrees C) will improve the evaporator heat
transfer, raise the suction pressure, and improve
chiller efficiency. Chilled water pump energy will
also be reduced.
Condenser entering water temperature
As a general rule, a one-degree drop in condenser
entering water temperature will reduce chiller
energy consumption by two percent. Cooler water
lowers the condensing pressure and reduces
compressor work. One or two degrees can make a
noticeable difference. The incremental cost of a
larger tower can be small and provide a good
return on investment.
Condenser water temperature rise
The industry standard of 3 gpm/ton or about a 9.5-
degree delta-T seems to work well for most
applications. Reducing condenser water flow to
lower pumping energy will increase the water
temperature rise, resulting in an increase in the
compressors condensing pressure and energy
consumption. This is usually not a productive
strategy.
Chilled Water Temperature
The maximum temperature of water entering the
chiller on standby must not exceed 110 F (43 C).
Maximum temperature entering on start-up must
not exceed 90F (32.2C). Minimum chilled water
leaving temperature without antifreeze is
approximately 36F (2.2C).
Piping
Piping must be adequately supported to remove
weight and strain on the chillers fittings and
connections. Be sure piping is adequately
insulated. Install a cleanable 20-mesh water
strainer at the inlet of the evaporator and
condenser. Install enough shutoff valves to permit
draining water from the evaporator or condenser
without draining the complete system.
Do use PVC or CPVC piping for any water lines.
Should a refrigerant-to-water leak occur, POE
lubricant in the refrigerant can have an adverse
effect on the pipe.