Power Factor Correction
Do not use power factor correction capacitors with
WMC chillers. Doing so can cause harmful
electrical resonance in the system. Correction
capacitors are not necessary since VFDs inherently
maintain high power factors.
The full load power factor exceeds 0.90 for all
units.
VFD Line Harmonics
Despite their many benefits, care must be taken
when applying VFDs due to the effect of line
harmonics on the building electric system. VFDs
cause distortion of the AC line because they are
nonlinear loads, that is, they don't draw sinusoidal
current from the line. They draw their current from
only the peaks of the AC line, thereby flattening
the top of the voltage waveform. Some other
nonlinear loads are electronic ballasts and
uninterruptible power supplies.
Line harmonics and their associated distortion can
be critical to ac-drives for three reasons:
1. Current harmonics can cause additional
heating to transformers, conductors, and
switchgear.
2. Voltage harmonics upset the smooth
voltage sinusoidal waveform.
3. High-frequency components of voltage
distortion can interfere with signals
transmitted on the AC line for some
control systems.
The harmonics of concern are the 5
th
, 7
th
, 11
th
, and
13
th
. Even harmonics, harmonics divisible by three,
and high magnitude harmonics are usually not a
problem.
Current Harmonics
An increase in reactive impedance in front of the
VFD helps reduce the harmonic currents. Reactive
impedance can be added in the following ways:
1. Mount the drive far from the source
transformer.
2. Add line reactors. They are standard
equipment on Magnitude chillers.
3. Use an isolation transformer.
4. Use a harmonic filter.
Voltage Harmonics
Voltage distortion is caused by the flow of
harmonic currents through a source impedance. A
reduction in source impedance to the point of
common coupling (PCC) will result in a reduction
in voltage harmonics. This can be done in the
following ways:
1. Keep the PCC as far from the drives
(close to the power source) as possible.
2. Increase the size (decrease the
impedance) of the source transformer.
3. Increase the capacity (decrease the
impedance) of the busway or cables from
the source to the PCC.
4. Make sure that added reactance is
"downstream" (closer to the VFD than
the source) from the PCC.
Line Reactors
Five-percent line reactors are standard equipment
on Magnitude chillers and located in each
compressors power panel. They are employed to
improve the power factor by reducing the effects
of harmonics.
Harmonic Filter
The harmonic filter is an option for field mounting
and wiring outside of the power panel. It works in
conjunction with the line reactor to further
minimize harmonic distortion. IEEE 519-1991
Standard defines acceptable limits.
See the Magnitude installation manual and
certified drawings for harmonic filter installation
information.
EMI (Electro Magnetic Interference) and RFI
(Radio Frequency Interference) Filter
This filter is a factory-installed option. The terms
EMI and RFI are often used interchangeably. EMI
is actually any frequency of electrical noise,
whereas RFI is a specific subset of electrical noise
on the EMI spectrum. There are two types of EMI.
Conducted EMI is unwanted high frequencies that
ride on the AC wave form.
EMI-Radiated EMI is similar to an unwanted
radio broadcast being emitted from the power
lines. There are many pieces of equipment that can
generate EMI, variable frequency drives included.
In the case of variable frequency drives, the
electrical noise produced is primarily contained in
the switching edges of the pulse width modulation
(PWM) controller.
As the technology of drives evolves, switching
frequencies increase. These increases also increase
the effective edge frequencies produced, thereby
increasing the amount of electrical noise.