42 Catalog 602-2
Condenser Water
Temperature
When the ambient wet bulb temperature is lower
than design, the entering condenser water
temperature can be allowed to fall, improving
chiller performance. As chillers are selected for
lower kW per ton, the cooling tower fan motor
power becomes a higher percentage of the peak
load chiller power. To obtain the lowest possible
energy cost, the interaction between compressor
power, fan power, and pumping power should all
be studied.
Even with tower fan control, some form of water
flow control such as tower bypass or variable
speed condenser water flow may be required to
maintain minimum acceptable entering condenser
water temperatures. must be used. The MicroTech
II control is capable of controlling tower fans and
bypass valve directly or indirectly through an
output signal to the building automation system
ensure stable and efficient chiller operation.
Figure 15 and Figure 16 illustrate two temperature
actuated tower by
pass arrangements. The “Cold
Weather” scheme, Figure 16, provides better
startup under cold am
bient air temperature
conditions. The bypass valve and piping are
indoors and thus warmer, allowing for warmer
water to be immediately available to the
condenser. The check valve may be required to
prevent air at the pump inlet.
Figure 15, Tower Bypass, Mild Weather
Operation
Figure 16, Tower Bypass, Cold Weather
Operation (Bypass Indoors)
Pumps
To avoid the possibility of objectionable
harmonics in the system piping, 4-pole,
1800/1500 rpm system pumps should be used.
The condenser water pump(s) must be cycled
off when the last chiller of the system cycles
off. This will keep cold condenser water from
migrating refrigerant to the condenser. Cold
liquid refrigerant in the condenser can make
start up difficult. In addition, turning off the
condenser water pump(s) when the chillers are
not operating will conserve energy.
Include thermometers and pressure gauges at
the chiller inlet and outlet connections and
install air vents at the high points of piping.
Where noise and vibration are critical and the
unit is mounted on spring isolators, flexible
piping and conduit connections are necessary.
Install a flow switch or pressure differential
switch in the leaving chilled water line, if one is
not factory installed.
Variable Speed Chilled
Water Pumping
Variable speed pumping involves changing
system water flow relative to cooling load
changes. Daikin McQuay centrifugal chillers
are designed for this duty with two limitations.
First, the rate of change in the water flow needs
to be slow, not greater than 10% of the change
per minute. The chiller needs time to sense a
load change and respond.
Second, the water velocity in the vessels must
be 3 to 10 fps (0.91 and 3.0 m/sec). Below 3 fps
(0.91 m/sec), laminar flow occurs which
reduces heat transfer and causes erratic
operation. Above 10 fps (3.0 m/sec),
excessively high pressure drops and tube
erosion occur. These flow limits can be
!
CAUTION
Freeze Notice: The evaporator and
condenser are not
self-draining. Both must
be blown out to completely remove water
to help prevent freeze up.