EDUS04-906_b Optional Accessories
Room Air Conditioners H-Series 77
3P157704-2B
4.Switch Settings
5.Control Codes
7.Combining Equipment
6.Read Operating / Error Display Signal
Tu rn the power on after all the switches have been set.
Settings made while the power is on are invalid.
NOTE
Overseas ON
“Automatic” operation is available from the central controller.
Japan
Destination
SW3-3 setting What Happens
OFF
(Factory setting)
Open the Kit’s case and set the switches on the circuit board.
(1) For Overseas / Japanese unit setting (SW3-3)
Room air conditioners, different methods are used for setting the temperature in
automatic mode, so this switch needs to be set.
When using a central remote controller, the operating codes can be used to limit
operation from wireless remote controllers.
: permitted; ´ : prohibited
The Operating / error signals can be read from the contact output (S5).
Output specs
M1: Tu rn MR 1 ON when the air conditioner is running.
M2: Turn MR 2 when a communication error has occurred between the KRP928B2S and
the air conditioner, or MR 1 is ON and the unit has stopped after an error.
MR 2 is not turned ON during a warning.
(2) Group number settings (SW1 and SW2-1 to SW2-3)
Set these when using the central controller. (Set to the side.) Do not set more
than one unit to the same number.
However, these settings do not need to be made when using the schedule timer
independently.
(The settings are needed when used in conjunction with another DCS Series
central controller.)
In this case, the schedule timer performs an auto address after the power is turned
on, so new group numbers are automatically set. Settings made using the switches
will be overwritten.
(3) Settings when recovering from a power outage (SW2-4)
This selects whether to restart operation when the power comes b
ack on after a
power outage occurred during operation. This setting is given priority in cases
where the indoor unit has an auto start ON / OFF jumper. Note also that
regardless of whether switch SW2-4 is on or off, the operating mode, set
temperature, fan direction and speed settings, and remote control prohibition
status are stored.
NOTE1: Since central equipment and HA JEM-A-compatible equipment both use
last command priority, the contact status and operating status of the air
conditioner might not match sometimes.
Example: If the unit is run from the central controller while the air
conditioner is stopped with an open contact, the contact will be
open and the unit will be running.
NOTE2: Operating mode and fan direction and speed settings can be changed.
(4) Contact input function settings (SW3-1 to SW3-2)
When using contact input (S1), choose one of the following fu
nctions.
NOTE also that a separate timer power source is needed when using the
schedule timer independently.
Po wer source specs: DC 16V, +10%, -15%, 200mA.
Recommended power source: Omron S82J-01015A. (Should be used with the
output voltage adjusted to the center, DC 16V.)
Upper
group NO.
1—
2—
3—
4—
5—
6—
7—
8
1
123
0
123
123
123
123
123
123
123
SW1
setting
Lower
group NO.
00
01
02
03
04
05
06
07
1
123
0
123
123
123
123
123
123
123
4
4
4
4
4
4
4
4
SW1
setting
Lower
group NO.
0 8
09
10
11
12
13
14
15
123
123
123
123
123
123
123
123
4
4
4
4
4
4
4
4
Stops if the unit was stopped before the power outage
and runs if it was running.
Stops after recovering from a power outage
OFF
(Factory setting)
ON
SW2-4 setting What Happens
ON / OFF control is rejected
(operate / stop / timer prohibition)
(NOTE 2).
During a forced stop, all
remote controller actions
are prohibited.
Last command priority
Contact - Open to close: air condition stops
(forced stop). Close to open: no change in
operating status.
Contact - Open to close: air condition runs.
Close to open: air conditioner is stopped
(NOTE 1).
Constant contact input
Forced stop or remote
controller permission input
The operating status of the air conditioner
is reversed by an instantaneous input of
100 msec or more.
Instantaneous contact
input (factory setting)
What Happens Control mode
S1
operating mode
SW3-2
setting
SW3-1
setting
OFF
OFF
ON
ON
Invalid
Run / stop Input
Contact specs
No-voltage minute electric current contact
(Minimum applicable load DC 12V, 1mA or lower)
Total wire length max: 328 ft (100 m)
KRP928B2S
S1
CA
CB
Forced stop
Timer operation
is accepted by
remote controller
Last command priority
Only OFF control
is accepted
ON / OFF control
is rejected
Control mode
Constant
contact mode
Instantaneous
contact mode
S1
operating
mode
Operations from
central controller,
contact input and
HA JEM-A input
10,11
6,7
8
9
2
12–19
0,1,3
4
5
4
8
2,10-19
0,1,3,5-7
Control
code
“Stop” control from the
central controller
“Run” control from the
central controller
Operations from the remote controller
´´
´
´´
´
´´
Central priority
´
´
*
**
´
´
´
´
´
´
´
´
´
´´
´
´
*
**
´
´
´´
´
´
*
´
´
´
´
´
´
Run / timer
Run / timer
Fan direction
and fan speed
Fan direction
and fan speed
Stop
Stop
Operating mode
temperature
Operating mode
temperaturet
´
Wireless Remote Controller
´´
Wired Remote Controller
´
HA JEM-A-compatible equipment

´´´
Instantaneous contact input
´´´
Constant contact input
´´´
Forced stop contact input
´´
D-BIPS
´´
Schedule timer
ON / OFF controller
ON / OFF controller
Central Remote Controller
S8 Power supply for relay (DC 12V)
Power source
for display
Relay specs (MR1 and MR2)
Coil voltage: DC 12V
Coil resistance: 160 10%
(Matsushita Electric HC
Relay, Omron MY Relay )
Wiring length
Max: 328 ft (100 m)
KRP928B2S
S5
MC
M1
M2
(+)
(–)
(–)
MR1
MR2
Operating Display
Abnormality display
Operating control panel (Field supply)
MR1
MR2
The remote controller permission / prohibition settings using the Ve-up controller are as
follows.
: permitted; ´ : prohibited
Forced stop
Constant
contact mode
Constant
contact mode
Instantaneous
contact mode
Instantaneous
contact mode
Last command
priority
Does not affect settings
permitted/prohibited
permitted/prohibited
´
´
´
´´
prohibited
permitted
prohibited
permitted
´´ ´´
Operations from
central controller,
contact input and
HA JEM-A input
permitted/prohibited
permitted/prohibited
permitted
prohibited
´

´
prohibited
permitted
Only OFF
control is
accepted
permitted/prohibited
permitted/prohibited
permitted
prohibited
´
´
´
´´´
´
´
´

prohibited
permitted
ON / OFF
control is
rejected
Start / stop
Change operating
mode
Change set
temperature
Run / timer
Operating mode
temperature
Fan direction
and fan speed
Stop
Operations from the remote controllerVe-up controller settings
Instantaneous
contact mode
Constant
contact mode
S1 pin
operating mode
permitted/prohibited
permitted/prohibited
´
´
´
´
´
prohibited
permitted
“Automatic” operation is not available from the central controller.
When using “automatic” operation using the wireless remote
controller, the central controller displays automatic cooling
(heating) and 77 °
F(25°C). Even if the temperature is changed, it
will return to 77°F (25°C) after a while.
SW2
setting
Central Remote Controller
Schedule timer
D-BIPS
Forced stop contact input
Constant contact input
Instantaneous contact input
HA JEM-A-compatible equipment
Wired Remote Controller
Wireless Remote Controller
The central controller can be combined with the following devices.
9
*
´
´
´
*Only during timer operation