EDUS04-906_b Electric Characteristics
Room Air Conditioners H-Series 19
10.Electric Characteristics
3D063013
Representative Unit Combination Power Supply COMP OFM IFM
Indoor Unit Outdoor Unit Hz-Volts Voltage Range MCA MOP RHz RLA W FLA W FLA
FTXG09HVJU RXG09HVJU
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
14.5 15 29
2.3
60 0.10 57
0.13
60-230 2.1 0.12
FTXG12HVJU RXG12HVJU
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
14.5 15 43
3.7
60 0.13 57
0.15
60-230 3.3 0.14
FTXG15HVJU RXG15HVJU
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
14.5 15 54
5.1
60 0.13 57
0.17
60-230 4.6 0.15
Symbols: Note:
MCA : MIN. CIRCUIT AMPS (A) 1. RLA is based on the following conditions.
Indoor temp. : 80°FDB / 67°FWB (26.7°CDB / 19.4°CWB)
Outdoor temp. : 95°FDB (35°CDB)
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. Be sure to install a ground leak detector. (One that can handle
higher harmonics.)
(This unit uses an inverter, which means that it must be used a
ground leak detector capable handling high harmonics in order to
prevent malfunctioning of the ground leak detector itself.)
MOP : MAX. OVERCURRENT PROTECTION (A)
RLA : RATED LOAD AMPS (A)
OFM : OUTDOOR FAN MOTOR
IFM : INDOOR FAN MOTOR
FLA : FULL LOAD AMPS (A)
W : FAN MOTOR RATED OUTPUT (W)
RHz : RATED OPERATING FREQUENCY (Hz)