Optional Accessories EDUS04-906_b
76 Room Air Conditioners H-Series
13.2.2 KRP928B2S
Safety Precautions
Read these Safety Precautions carefully to ensure correct installation.
This manual classifies precautions into WARNING and CAUTION.
WARNING :
Failure to follow WARNING is very likely to result in such grave
consequences as death or serious injury.
CAUTION : Failure to follow CAUTION may result in serious injury or
property damage, and in certain circumstances, may result in
a grave consequence.
Be sure to follow all the precautions below ; they are all important for
ensuring safety.
3.Names of Parts and Electric Wiring
WARNING
CAUTION
After installation is complete, test the operation of the PCB set to check
for problems, and explain how to use the set to the end-user.
1.Overview, Features and Compatible Models
This kit is the interface required when connecting the central controller and a Daikin Room Air
Conditioner. Use of the central controller makes it possible to perform the following monitoring
and operations. It is compatible with room air conditioners which have an HA connector S21.
Precaution
1.When reading the Operating / error signals, a separate external power source
(DC 12V) is needed.
2.A separate timer power source (DC 16V) is needed when using the schedule
timer independently, and not in conjunction with other central controllers.
3.The range of temperatures that can be set from the central controller is 18°C to
32°C in cooling and 14°C to 28°C in heating.
4.
Fan operation cannot be selected from the central controller or wired remote controller.
5.
Group control (i.e., control of multiple indoor units with a single remote controller) is
not available.
6.Monitoring is not available of the thermo status, compressor operating status,
indoor fan operating status, electric heater, or humidifier operating status.
7.Forced thermo off, filter sign display and reset, fan direction and speed settings,
air conditioning fee management, energy savings instructions, low-noise
instructions, and demand instructions cannot be made.
1.Run / stop for the central controller and wired remote controller, operating mode
selection, and temperature can be set.
2.The operating status, any errors, and the content of those errors can be monitored
from the central controller and wired remote controller.
3.Run / stop for the central controller and wireless remote controller, operating mode
selection, and the temperature setting can be limited by the central controller.
4.Zone control can be performed from the central controller.
5.The unit can remember the operating status of the air conditioner before a power
outage and then start operating in the same status when the power comes back
on.
6.Card keys, operating control panels, and other constant / instantaneous
connection-compatible equipment can be connected.
7.The Operating / error signals can be read.
8.HA JEM-A-compatible equipment can be connected.
9.The indoor temperature can be monitored from the Ve-up controller.
2.Component Parts and Separately-Sold Parts which are Required
This kit includes the following components. Check to ensure that none of
these are missing.
1234 1234
1234
1
0
ON
OFF
ON
OFF
SW1
S16
S19
S6
F1
SW2
SW3
LED1
Tes1
S1 S8 S5
F2
Once the switches are set and
the wiring complete, secure the
case using the included
screws.
A cable field supply A cable field supply
In case that the device coping
with HA JEM-A is connected
Connecting a Wired
Remote Controller
In case that a central remote
controller is connected
Connecting a Momentary / constant
Contact Input Equipment
Reading the Operating / error Display
Tele-con (Field supply)
Remote controller
BRC944 Series
Card key
(Field supply)
Operating control panel
(Field supply)
KRC65, KRC72,
KDC100A10, and KDC101B
Series cannot be connected.
The adapter included with the
remote controller is not used.
DAIKIN
<Wiring procedure>
Supplied connection harness
Installation should be left to the dealer or another qualified professional.
Improper installation by yourself may cause malfunction, electrical shock, or fire.
Install the set according to the instructions given in this manual.
Incomplete or improper installation may cause malfunction, electrical shock, or fire.
Be sure to use the standard attachments or the genuine parts.
Use of other parts may cause malfunction, electrical shock, or fire.
Disconnect power to the connected equipment before starting installation.
Failure to do so may cause malfunction, electrical shock, or fire.
An earth leakage circuit breaker should be installed.
If the breaker is not installed, electrical shock may occur.
Do not install the set in a location where there is danger of exposure to
inflammable gas.
Gas accumulated around the unit at the worst may cause fire.
To prevent damage due to electrostatic discharge, touch your hand to a
nearby metal object (doorknob, aluminum sash, etc.) to discharge static
electricity from your body before touching this kit.
Static electricity can damage this kit.
Lay this cable separately from other power cables to avoid external
electrical noises.
Screw cover
Non polarity
Included in the Drain
Up Kit.
Separately sold remote control code (quadplex)
KRCW101A Series
Operating monitoring
equipment
(Field supply)
Parts
Kit assy
PCB is in the housing.
Q’ty Q’ty
1
Parts
Connection harness (about 1.6m)
Mounting screws
Binding band
Installation manual
1set
3pcs.
1pc.
1set
Room air conditioner indoor unit
To HA connector (S21)
Cable available field supply
(See the installation manual of
the central remote controller)
Lower group number
switch (SW1)
Upper group number
switch (SW2-1to 3)
Operation when recovering
from a power outage mode
switch (SW2-4)
Service monitor (LED1: green)
When the CPU is working
properly, the LED flashes.
Power supply terminal (S8)
Connect an external DC 12V power
supply only when reading the
Operating / error display.
Japanese unit / Overseas unit
Setting switch (SW3-3)
Momentary contact / constant contact
Selection switch (SW3-2)
Forced stop
Settings switch (SW3-1)
Central controller equipment
DCS302 Series
DCS301 Series
DCS601 Series
DST301 Series