Daikin REYQ168 Installation Manual Page 68

  • Download
  • Add to my manuals
  • Print
  • Page
    / 248
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 67
Installation SiUS39-506
62 General Information
Bolt pitch
Caution in installation
1. Execute the installation work by checking the foundation strength and levelness to avoid any occurrence of
vibration and noise.
Fix the unit tightly with foundation bolts. (Prepare 4 sets of M12 foundation bolts with proper nuts and
washers.)
The proper length of the foundation bolts form the surface of the base is 13/16".
Caution
Install the unit securely in case of earthquake an typhoon, cyclone, hurricane or other strong wind. The unit
may topple or cause another accident if improperly set up.
Unpacking and
Placing the Unit
Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise.
Secure the unit to its base using foundation bolts. (Use four commercially available M12-type
foundation bolts, nuts, and washers.)
The foundation bolts should be inserted 13/16".
Make sure the base under the unit extended more than 30 1/8" behind the unit.
The height of the base should be at least 5 7/8" from the floor.
The unit must be installed on a solid longitudinal foundation (steelbeam frame or concrete) as
indicated in the figure below.
DO NOT USE STANDS TO SUPPORT THE CORNERS
REYQ96MTJU
43 3/8
4-φ19/32" dia. holes
28 7/16-29"
Model A (in.) B (in.)
Q96 type 48 13/16 43 3/8
13/16
28 7/16 - 29
3 1/83 1/8
30 1/8
A
B
1
2
3
(in.)
1. Foundation bolt point (φ9/16"
dia. : 4 positions)
2. Depth of product
3. Shape of indoor units support
leg and foundation bolt
positions
1. Do not use stands to support four
corners.
2. Center position of unit
Page view 67
1 2 ... 63 64 65 66 67 68 69 70 71 72 73 ... 247 248

Comments to this Manuals

No comments