Refrigerant Piping Work SiUS39-506
196 Installation Manual BS Unit
For locally procured insulation, be sure to insulate all the way to the pipe connections inside the
machine.
Exposed piping may cause condensation to form or burns on contact.
Use the following material specification for refrigerant piping:
(1) construction material: Phosphoric acid deoxidized seamless copper for refrigerant.
(2) size: Determine the proper size referring to chapter SELECTION OF PIPE CONNECTION
SIZE
(3) The wall thickness of the refrigerant piping should comply with relevant local and national
regulations.
Ventilate if refrigerant gas leaks while performing work.
Finally make sure there is no refrigerant gas leak. A toxic gas may be released by the refrigerant
gas leaking indoor and being exposed to flames from an area heater, cooking stove, etc.
Table 1
Table 2
Pipe gauge
(in)
Tightening torque (ft-lbf)
Flare dimension
A (in)
Flare shape (in)
1/4’’ 10.5 12.7 0.343 0.358
3/8’’ 24.1 29.4 0.504 0.520
1/2’’ 36.5 44.5 0.638 0.654
5/8’’ 45.6 55.6 0.760 0.776
Pipe size
(in)
Further tightening angle (degree) Recommended arm length of tool (in)
1/4’’ 60 to 90 Approx. 5 7/8’’
3/8’’ 60 to 90 Approx. 7 7/8’’
1/2’’ 30 to 60 Approx. 9 13/16’’
5/8’’ 30 to 60 Approx. 11 13/16’’
Spanner
Piping union
Torque wrench
Flare nut
Fig. 2
Coat here with ether oil or ester oil.
Fig. 3
Insulation
(locally procured)
Wrap around top
of flare nut
Clamp 2)
Insulation for fitting
(Attached) 3)-1
Insulatoin for fitting
(Attached) 3)-3
(For liquid pipe)
(For gas pipe)
Gas piping
Liquid piping
Fig. 4
Part to be
brazed
Taping
Pressure-reducing valve
Nitrogen
Valve
Refrigerant piping
Nitrogen
Fig. 5
45
0
2
0
90
0
2
0
R 0.016~0.031
A
Page view 201