194 Installation Manual BS Unit
5. BS Unit Installation
(1) Attach the hunger brackets to the suspension bolts.
Be sure to sandwich the hunger brackets between nuts and
washers, and securely fix it.
CAUTION
The BS unit has a top and a bottom, so install it so that the diagonal lines in the figure next page
are where the top is. (Failing to do so may prevent the unit from operating properly and increase
the volume of the operating noise.)
(2) The electric parts box may be installed on either side of the BS unit, as shown below.
1.Remove the electric parts box lid. (2 screws)
2.Remove the top panel. (4 screws)
3.Remove the electric parts box. (2 screws)
4.Change the way the wiring between the unit and the electric parts box (transformer, two
solenoid valve coils) is pulled out. (See the figure at next page.)
5.Attach the electric parts box.
6.Turn the top panel around 180° and attach it.
7.Attach the electric parts box lid.
Changing the installation position of the electric parts box
NOTE:
Install the BS unit according to the instructions shown on the name plate attached to the electric
parts box.
Clamp securely so the interior wiring does not touch the screws or sheet metal due to
looseness.
Nut
BS unit
proper
Washer
Suspension bolt
3/8 9/16
Hunger
bracket
2, 6
2, 6
Top Panel
Move the electric parts box
Electric parts box
Electric parts
box lid
1
1
3
3
2, 6
2, 6
5
5
7
7
<Changing the direction the
wiring is pulled out>
[Before change]
[After change]
Use the included clamping
material 2) to tie excess
lead wire so it does not droop.