Daikin REYQ168 Installation Manual Page 57

  • Download
  • Add to my manuals
  • Print
  • Page
    / 248
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 56
SiUS39-506 Installation
General Information 51
Ceiling
Suspended Type
(FXHQ-M)
(1) Carry out the drain piping.
Make sure piping provides proper drainage.
You can select whether to bring the drain piping out from the rear right or right. For rear right-
facing and right-facing situations, refer to 6. REFRIGERANT PIPING WORK on page 7.
Make sure the pipe diameter is the same or bigger than the branch piping. (vinyl-chloride piping,
nominal diameter 1 in., external diameter 1 1/4 in.)
Make sure the piping is short, has at least a 1/100 slope, and can prevent air pockets from
forming. (Refer to Fig. 21)
Do not allow any slack to gather in the drain pipe inside the indoor unit.
(Slack in the drain pipe can cause the suction grille to break.)
Caution Water accumulating in the drain piping can cause the drain to clog.
Be sure to use the drain pipe (1) and metal clamp (2).
Also, insert the drain pipe completely into the drain socket, and securely attach the metal clamp
bracket inside the gray tape area on the inserted tip of the drain pipe. (Refer to Fig. 22)
Screw the screws on the metal clamp bracket until there is 5/32 in. left. (Pay attention to the
direction of the attachment to prevent the metal clamp bracket from coming into contact with the
suction grille.) (Refer to Fig. 23)
Insulate the metal clamp bracket and drain pipe from the bottom using the large sealing pad (8).
(Refer to Fig. 23)
Be sure to insulate all drain piping running indoors.
Note: To ensure no excessive pressure is applied to the drain pipe (1), do not bend or twist when
installing. (This may cause leakage.)
Tilt down
Do not lift
Make sure there
is no slack
Make sure it is
not in the water
Good
Wrong
Fig. 21
Taping area (Gray)
Drain pipe (1)
Metal clamp (2)
Fig. 22
Large sealing pad (8)
Metal clamp (2)
< Facing rear right or right >
5/32 or less
Fig. 23
(Length : in.)
Page view 56
1 2 ... 52 53 54 55 56 57 58 59 60 61 62 ... 247 248

Comments to this Manuals