50 General Information
Ceiling Mounted
Duct Type
(FXMQ-M)
Note: If installing central drain piping, install according to the following right figure.
(Install a drain trap for each indoor unit.)
After piping work is finished, check drainage flows smoothly.
<<Rig the drain pipe as shown below and take measures against
condensation. Improperly rigged piping could lead to leaks and
eventually wet furniture and belongings.>>
<<Insulate the drain hose inside the buildings>>
(1) Install the drain pipes.
Keep piping as short as possible and slope it downwards so that air may not
remaine trapped inside the pipe.
Keep pipe size equal to or greater than that of the connecting pipe (Vinyl pipe of 1"
norminal diam. and 1 1/4" outer diam.).
Use the attached drain hose and clamp.
Tighten the clamp firmly.
Insulate the clamp metal with the attached sealing pad.
There is negative pressure inside the unit relative to atmospheric pressure
when the unit is running, so be sure to provide drain frap on the drain outlet.
(See the figure)
In order to prevent foreign matter from building up inside the piping, you
should avoid curves as much as possible, and arrange so the trap can be
cleaned.
FXMQ30-48M
1 15/16"
1 15/16"
1