Installation SiUS39-506
48 General Information
Ceiling Mounted
Built-in Type
(FXSQ-M)
Drain Piping
Rig the drain pipe as shown below and take measures against condensation. Improperly rigged
piping could lead to leaks and eventually wet furniture and belongings.
(1) Rig drain piping
The diameter of the drain pipe should be greater than or equal to the diameter of
the connecting pipe (vinyl tube; pipe size: 1" ; outer dimension: 1 1/4").
Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent
air pockets from forming.
If the drain hose cannot be sufficiently set on a slope, execute the drain raising
piping.
To keep the drain hose from sagging, space hanging wires every 40 to 60".
Caution
Setting the unit at an angle opposite to the drain piping might cause leaks.
Use the attached drain hose and clamp metal. Tighten the clamp firmly. Insert the
drain hose into the drain socket, up to the white tape. Tighten the clamp until the
screw head is less than 3/16" from the hose.
Wrap the attached sealing pad over the clamp and drain hose to insulate.
Insulate the drain hose inside the building.
PRECAUTIONS FOR DRAIN RAISING PIPING
HOW TO INSTALL PIPING
(1) Connect the drain hose to the drain raising pipes, and insulate them.
(2) Connect the drain hose to the drain outlet on the indoor unit, and tighten it with
the clamp.
(3) Insulate both metal clamp and drain hose with the attached sealing pad.
No Good Good
A
When canvas duct
is installed
13 3/4~20 7/8"
When air inlet panel
is directly installed
10 13/16"
3/16"
Large sealing pad
Clamp metal
(attached)
(attached)
Clamp metal
Drain hose
Tape (White)
A
Drain raising pipe
Clamp (Attached with unit)
Drain hose (Attached with unit)
Ceiling slab
11 13/16"
or less
Hanging bar
Adjustable range
(0 9 13/16 ")
Part to be procured
in the field
3.28~4.92 ft