Appendix SiUS39-506
106 General Information
7.2 Allowable Piping Length
7.2.1 Branch with refnet joint
(Connection of 8 indoor units Heat pump system)
Piping from BS unit to indoor unit and piping from refrigerant branch kit to indoor unit used as
cooling only must be composed by 2 pipes (Suction Gas pipe and Liquid pipe)
* If case of multiple outdoor units installed, re-read to the first outdoor branch as seen from the
indoor unit.
One outdoor
unit installed
Branch with refnet joint
Multiple
outdoor units
installed
12 34
B2B1 B3 B4
567
7
6
1
6
8
H2
H1
a
b
c
l
n
oq
r
s
p
m
ki
f
g
j
h
de
REFNET joint ( ~ )Outdoor unit
BS unit
Indoor unit
B1 B4
Cooling only
(
.
)
Cool/Heat selection possible
( ~
)
( ~ )
1
( ~ )
8
A
B
CDE
A
E
Maximum
allowable
length
Between outdoor and indoor units
• Actual pipe length
Pipe length between outdoor and indoor units ≤ 330ft.
Example unit 8: a + b + c + d + e + s ≤ 330ft.
• Equivalent length
Equivalent pipe length between outdoor and indoor units ≤ 390ft.
(assume equivalent pipe length of refnet joint to be 1.6ft., that of refnet header to be 3.3ft.,
calculation purposes)
• Total extension length
Total piping length from outdoor unit* to all indoor units ≤ 950ft.