7.2 Allowable Piping Length
7.2.1 Branch with refnet joint
(Connection of 8 indoor units Heat pump system)
Piping from BS unit to indoor unit and piping from refrigerant branch kit to indoor unit used as
cooling only must be composed by 2 pipes (Suction Gas pipe and Liquid pipe)
* If case of multiple outdoor units installed, re-read to the first outdoor branch as seen from the
indoor unit.
One outdoor
unit installed
Branch with refnet joint
Multiple
outdoor units
installed
12 34
B2B1 B3 B4
567
7
6
1
6
8
H2
H1
a
b
c
l
n
oq
r
s
p
m
ki
f
g
j
h
de
REFNET joint ( ~ )Outdoor unit
BS unit
Indoor unit
B1 B4
Cooling only
(
.
)
Cool/Heat selection possible
( ~
)
( ~ )
1
( ~ )
8
A
B
CDE
A
E
Maximum
allowable
length
Between outdoor and indoor units
Actual pipe length
Pipe length between outdoor and indoor units 330ft.
Example unit 8: a + b + c + d + e + s 330ft.
Equivalent length
Equivalent pipe length between outdoor and indoor units 390ft.
(assume equivalent pipe length of refnet joint to be 1.6ft., that of refnet header to be 3.3ft.,
calculation purposes)
Total extension length
Total piping length from outdoor unit* to all indoor units 950ft.