SiUS39-506 Appendix
General Information 111
Between outdoor branch and outdoor unit (Only for multiple outdoor units)
Actual pipe length
Piping length from outdoor branch to outdoor unit 33ft. Equivalent length: max 43ft.
r 33ft. (Equivalent length: max 43ft.)
t 33ft. (Equivalent length: max 43ft.)
Allowable
height
length
Between outdoor and indoor units
Difference in height
Difference in height between outdoor and indoor units (H1) 164ft.
(Max 130ft. if the outdoor unit is below)
Between indoor and indoor units
Difference in height
Difference in height between adjacent indoor units (H2) 49ft.
Between outdoor and outdoor units
Difference in height
Difference in height between outdoor unit (main) and outdoor unit (sub) (H3) 16ft.
Allowable
length after
the branch
Actual pipe length
Pipe length from first refrigerant branch kit (either refnet joint or refnet header) to indoor unit 130ft.
Example unit 8: o 130ft.