REFNET Pipe System EDUS39-606A-N
6 Installation of Outdoor Units
When the number of indoor units to be connected to the branch pipes is less than the number of branch pipes
available for connection then cap pipes should be fitted to the surplus branches.
When the size of the selected field piping is different from that of branch pipe, you must cut the connecting section
with a pipe cutter as shown in the following figure:
When field piping is connected to the B section of the inlet/outlet pipe on the outdoor unit side of the liquid pipe
header, cut the B section with a pipe cutter and connect it to the A section.
.
Connect the flared section of the field pipe to the B section, as shown in the following figure:
Fit the branch pipe so that the branch lies in a horizontal plane.
The branch pipe must be insulated in accordance with the instruction manual accompanying each kit.
1. Insulate the header with insulator included in the kit.
2. Joints between insulators included in the kit and those already applied to the field piping should be sealed with the
tape accompanying each kit.
3. Any cap pipes should also be insulated using the insulator provided with each kit and then taped as described above.