Daikin RXYMQ36MVJU Instruction Manual Page 14

  • Download
  • Add to my manuals
  • Print
  • Page
    / 31
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 13
EDUS39-606A-N Installation
Installation of Outdoor Units 13
(3) When installing the outdoor unit in a location with
heavy snowfall, pay special attention to the following
items:
Prepare strong foundation.
Attach the snow hood (optional accessory).
Remove the suction grill on the rear so that snow will
not be accumulated in the rear fin.
(4) When there is a possibility of short-circuitry depend-
ing on the ambient situation, use the wind direction
adjusting plate (optional accessory).
(5) The inverter type air conditioner may cause noise in
electric products.
When selecting an installation location, keep sufficient
distance from the air-conditioner units and wiring to
radios, personal computers, stereos, etc. as shown in the
figure below.
In areas with weak electric waves, keep a distance of 120
inches or more from the indoor remote controller, put the
power cables and connection cables in conduit tubes, and
ground the conduit tubes.
40 or more
Branch switch
and overcurrent
breaker
Indoor remote
controller
60 or more
60 or more
40 or more
Branch switch
and overcurrent
breaker
60 or more
Indoor unit
(in.)
DANGER
Do not install unit in an area where flammable materials are
present due to risk of explosion resulting in serious injury or
death.
Refrigerant is heavier than air and replaces oxygen. A
massive leak could lead to oxygen depletion, especially in
basements, and an asphyxiation hazard could occur lead
-
ing to serious injury or death.
Installation place (numeric units: inches)
Cautions on continuous installation
The connection piping outlet direction in the continuous
installation shown in the figures below is frontward or
downward.
When routing the piping rearward, secure space of 10
inches (254 mm) or more on the right side of the outdoor
unit.
Make some space for wiring with conduit and servicing
between the units.
(A) When an obstruction is present on the air inlet side
When the upward area is open
(1) When one outdoor unit is installed individually
When an obstruction is present only on the air inlet
side
4 or more
When an obstruction is present on both sides
4 or more
4 or more
4 or more
Page view 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 30 31