EDUS39-606A-N Checks after Completion of Work
Installation of Outdoor Units 28
NOTE:
If nothing displays on the remote controller, there might be a
problem with the connection or transmission between the
indoor unit and the remote controller. Check connections, and
check for wire breakage.
After finishing the test operation and before using the unit by
customer, confirm that the outside panels and screws are
attached securely to the units.
5.1
Caution for Refrigerant Leaks
DANGER
Refrigerant gas is heavier than air and replaces oxygen. A
massive leak could lead to oxygen depletion, especially in
basements, and an asphyxiation hazard could occur lead
-
ing to serious injury or death.
CAUTION
The installer and system specialist must follow proce-
dures to prevent leakage according to local regulations
or standards. The following standards may be applicable
if local regulations are not available.
The VRV System, like other air conditioning systems, uses
R-410A which is an entirely safe non-toxic, non-combustible
refrigerant. Nevertheless care must be taken to ensure that
air-conditioning facilities are installed in rooms large enough
to ensure that in the unlikely event of a major leak, the maxi
-
mum concentration level of refrigerant gas is not exceeded.
Maximum concentration level:
The maximum charge of refrigerant and the calculation of the
maximum concentration of refrigerant is directly related to the
humanly occupied space in to which it could leak.
The unit of measurement of the concentration is lb./ft
3
or the
weight in lb. of the refrigerant gas in 1ft
3
volume of the occu-
pied space.
F6
The refrigerant is
overcharged.
Calculate again the required
amount of refrigerant to be
charged based on the piping
length, recover the refrigerant
using the refrigerant recovery
device, then achieve proper
amount of refrigerant.
U3
The check
operation has
not performed.
Perform the check operation.
U4
The power is not
supplied to the
outdoor unit.
Connect correctly the power
supply wiring of the outdoor
unit.
UA
Improper type of
indoor units are
connected.
Check the type of indoor units
currently connected. If they are
not proper, replace them with
proper ones.
UF
The stop valves
in the outdoor
unit remain
closed.
Open the stop valve on both the
gas and liquid lines.
The piping and
wiring of the
indoor unit are
not connected
correctly to the
outdoor unit.
Confirm that the piping and
wiring of the indoor unit are con-
nected correctly to the outdoor
unit.
The operation
mode on the
remote control-
ler was changed
before the check
operation.
Set the operation mode on all
indoor unit remote controllers to
COOLING.
UH
The transmis-
sion wiring is not
connected
correctly.
Connect correctly the transmis-
sion wiring to the F1 and F2
(TO IN/D UNIT) terminals on
the PC board (A1P) in the
outdoor unit.