EDUS39-606A-N Installation
Installation of Outdoor Units 15
(1) When one outdoor unit is installed individually
L
4 or more
H
20 or more
L>H
(2) When two or more outdoor units are installed side
by side
12 or more
H
L
40 or more
L>H
When an obstruction is also present in the upward
area
(1) When one outdoor unit is installed individually
L
A
20 or less
40 or more
10 or more
H
The dimensional relationship between H, L, and A is as
shown in the table below.
Close the area under the frame so that the outlet air does
not bypass there.
(2) When only two outdoor units are installed side by
side
A
H
L
20 or less
12 or more
40 or more
The dimensional relationship between H, L, and A is as
shown in the following table:
NOTE:
1. Close the area under the frame so that the outlet air
does not bypass there.
2. Only two outdoor units can be installed side by side.
<Pattern 2>
When an obstruction on the air outlet side is lower than the out-
door unit. There is no restriction in the height of obstruction on the
air inlet side.
When the upward area is open
(1) When one outdoor unit is installed individually
L
H
4 or more
20 or more
H
L
(2) When two or more outdoor units are installed side
by side
L
60 or more
H
A
The dimensional relationship between H, L, and A is as
shown in the following table:
When an obstruction is present also in the upward area
(1) When one outdoor unit is installed individually
L
40 or more
40 or more
20 or less
H
A
LA
L
H
0
<
L
1/2H 30
1/2H
<
L
H40
H
<
L
Install the frame to achieve L
H.
LA
L
H
0
<
L
1/2H 40
1/2H
<
L
H50
H
<
L
Install the frame to achieve “L
H”.
LA
0
<
L
1/2H 10
1/2H
<
L
H12