Installation EDUS39-606A-N
16 Installation of Outdoor Units
The dimensional relationship between H, L and A is as
shown in the following table:
NOTE:
Close the area under the frame so that the outlet air does
not bypass there.
(2) When only two outdoor units are installed side by
side
60 or more
20 or less
H
L
A
40 or more
The dimensional relationship between H, L and A is as
shown in the following table:
NOTE:
1. Close the area under the frame so that the outlet air
does not bypass there.
2. Only two outdoor units can be installed side by side.
(D) When outdoor units are stacked
(1) When an obstruction is present on the air outlet
side
4
Z
40 or more
NOTE:
1. Only two outdoor units can be stacked.
2. For drain treatment, a space of at least 4 inches is
required between upper and lower outdoor units.
3. Close the area Z (gap between the upper outdoor unit
and the lower outdoor unit) so that the outlet air does not
bypass there.
(2) When an obstruction is present on the air inlet side
4
Z
12 or more
NOTE:
1. Only two outdoor units can be stacked.
2. For drain treatment, a space of at least 4 inches is
required between upper and lower outdoor units.
3. Close the area Z (gap between the upper outdoor unit
and the lower outdoor unit) so that the outlet air does not
bypass there.
(E)
When outdoor units are installed in rows, such as on a
rooftop.
(1) When one outdoor unit is installed in each row
4 or more
8 or more
80 or more
40 or more
LA
L
H
0
<
L
1/2H 4
1/2H
<
L
H8
H
<
L
Install the frame to achieve L
H.
LA
L
H
0
<
L
1/2H 10
1/2H
<
L
H12
H
<
L
Install the frame to achieve L
H.