EDUS39-606A-N Installation
Installation of Outdoor Units 24
Power supply wiring connection procedure
WARNING
Never connect power supply wiring to the terminal block for
remote controller wiring as this could damage the entire
system.
Install a ground leakage circuit breaker.
You must install a ground leakage circuit breaker to pre-
vent electric shock and fire accident.
Stop valve
mounting plate
Power supply wiring
(including ground wire)
or
Transmission wiring
Power supply wiring
(including ground wire)
or
Transmission wiring
Electric parts
mounting plate
A1P
Transmission wiring
between units
Control PC
board (A1P)
Control
terminal
block
Ground wiring
(yellow/green)
Power
supply wiring
Terminal block
Clamp (accessory)
Pass the wiring
through the clips.
Power
terminal
block
TO IN/D UNIT
F2
TO OUT/D UNIT
F1F2F1
A
C/H SELECTOR
B
C
(X1M)
(X1M)
L1 L2
When using a
shield wire
Clamp (accessory)
Insulating tube (accessory)
This clamp is unnecessary when not
using shield wire.
Lock nut
Cover
Conduit
arrow view
Screw
Transmission wiring
between units
Cable clamp
(Copper foil is provided.)
Shield
Fix the shield area of the unit-
to-unit wiring to the copper foil
area of the clamp.
When using shield wire
CAUTION
After finishing the electrical wiring work, confirm that all the
wirings are connected securely.
Precautions when laying power wiring:
Two electric wires of different thickness cannot be con-
nected to the power terminal block.
Slack in the electric wires may generate abnormal heat.
Use round pressure terminals with insulting sleeve for con-
nection to the power terminal block.
If round pressure terminals are not available, connect an
electric wire of the same thickness to each side as shown in
the figure.
Power wire
Round pressure terminal
Attach insulation sleeve
Connect same-
thickness wiring
to both sides.
It is forbidden to
connect two to
one side.
It is forbidden to
connect wiring of
different thicknesses.
You must observe the following instructions or abnor-
mal heat may be generated by slack in electric wires.
For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure on the ter
-
minal board.
Use an appropriate screwdriver for tightening the terminal
screws.
A screwdriver with a small head will strip the head and
make proper tightening impossible.
Over-tightening the terminal screws may break them.
See the table below for tightening torque for the terminal
screws.
Model
Phase and
frequency
Voltage
Rated current
of fuse
Min. Circuit
Amps.
RXYMQ36MVJU
~ 60Hz 208-230V 30A 27A
RXYMQ48MVJU
Tightening torque
M5 (Power supply and ground terminal block)
1.76 ~ 2.15 ft-lbf
(536..4 ~ 655.32 mm)-lbf
M4 (Shielded ground)
0.87 ~ 1.06 ft-lbf
(265.17 ~ 323.09 mm-lbf)
M3.5 (Transmission wiring terminal block)
0.58 ~ 0.72 ft-lbf
(176.74 ~ 219.46 mm)-lbf