Daikin RXYMQ36MVJU Instruction Manual Page 23

  • Download
  • Add to my manuals
  • Print
  • Page
    / 31
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 22
EDUS39-606A-N Installation
Installation of Outdoor Units 22
1. Open the gas line stop valve (leaving the liquid line stop
valve, valve A in the diagram above, close) and perform the
operation to add the refrigerant.
2. Once the appropriate amount of refrigerant is in, press the
confirmation button (BS3) on the outdoor unit PC board
(A1P), and stop operation.Open the stop valves quickly
(both liquid and gas line valves).(This must be done quickly
to avoid the possibility that the pipe might burst.)
3. Stop Valve Operation Method Cautions:
The figure below shows the name of each part required in
handling the stop valve. At the time of shipment, the stop
valve is closed.
If only a torque wrench is used to loosen or tighten the flare
nut, the side plate may be distorted. Make sure to fix the
stop valve with a spanner, then loosen or tighten the flare nut
with a torque wrench.
When it is expected that the operating pressure will be low
(for example, when cooling will be performed while the out-
side air temperature is low), sufficiently seal the flare nut in
the stop valve on the gas line with silicon sealant to prevent
freezing.
Prepare hexagon wrenches .2 and .3 inches.
How to open the stop valve
1.Insert a hexagon wrench into the valve stem, and turn
the valve stem counterclockwise.
2.When the valve stem cannot be turned any more, stop
turning. Now, the valve is open.
How to close the stop valve
1.Insert a hexagon wrench into the valve stem, and turn
the valve stem clockwise.
2.When the valve stem cannot be turned any more, stop
turning. Now, the valve is closed.
Valve cap
Service port
Field piping
connection part
Valve stem
Silicon sealant
(Take care not to generate cavity.)
<Liquid line>
<Gas line>
Opening direction
Opening direction
Cautions Handling the Valve Cap:
The valve is sealed in the arrow area. Take care not to dam-
age the arrow area.
Valve cap
Stop valve
(valve cap attachment area)
After handling the valve, make sure to tighten the valve cap
securely.
Use the following precautions handling the service port:
Use charge hose equipped with push in the work.
After the work, make sure to tighten the valve cap securely.
Tightening torque.....8.5~10.3 ft·lbf
Note: Do not apply force to the valve cap.
Using a spanner on the valve cap and the valve
body could cause a refrigerant leak.
4.8 Electrical Wiring Work
DANGER
Do not ground units to water pipes, telephone wires, or
lightning rods because incomplete grounding could cause
a severe shock hazard resulting in severe injury or death,
and to gas pipes because a gas leak could result in an
explosion which could lead to severe injury or death.
WARNING
Disconnect all power to unit to avoid possible electric shock
during installation.
Use only specified wire and connect wires to terminals tightly. Be
careful that wires do not place external stress on terminals. Keep
wires in neat order so as to not to obstruct other equipment.
Incomplete connections could result in overheating, and in worse
cases, electric shock or fire. For details see Power Supply Wiring
Connection Procedure.
Liquid line Gas line
10.0~12.2 ft·lbf 16.6~20.3 ft·lbf
Spanner
prohibition to
valve cap and
body part
Stop valve of two
hangs stucture
Stop valve of one
hangs stucture
Torque
wrench
Torque
wrench
Spanner
Page view 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 29 30 31

Comments to this Manuals

No comments