Daikin RXYMQ36MVJU Instruction Manual Page 20

  • Download
  • Add to my manuals
  • Print
  • Page
    / 31
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 19
EDUS39-606A-N Installation
Installation of Outdoor Units 19
From that position, further tighten the flare nut the angle
shown below.
After the work is finished, make sure there is no gas
leak.
Disposal requirements
Dismantling of the unit and treatment of the refrigerant, oil, and
other parts should be comply should be in compliance with the
relevant local and national regulations. Refrigerant piping work
procedure:
The field piping can be connected in four directions.
Piping cover
Screw for
front panel
Screw for piping
cover (front)
Front
panel
Lateral
direction
Front direction
Rear
direction
Downward
direction
When connecting the piping in the lateral direction (on
the rear), remove the piping cover (rear) and receiver
mounting plate in reference to the figure below.
Receiver mounting plate
Piping cover (rear)
When connecting the pipings downward, remove the
knockout by making four holes in the middle on the
each side of the knockout with a drill.
Field pipings
Bottom frame
Knockout
Drill
Slit
Middle on the side
Slit
Then cut out the corner of the bottom frame along the
slits (in two positions) by using a hacksaw.
After removing the parts, paint the edges to prevent
rusting.
Ensure that the field pipings do not touch the terminal
cover of the compressor. Especially when the insula
-
tion provided on the liquid piping touches the terminal
cover, adjust its height as shown in the figure above.
Make sure that the piping does not touch the bolts of
the compressor and the outer panels.
When it is expected that condensed water in the stop
valve will reach the indoor unit through the gap
between the heat insulating material and the piping
(for example, when the outdoor unit is installed in a
higher position than the indoor unit), take proper
action such as caulking the connection area.
To prevent invasion of small creatures and litter: Block
all gaps in the piping penetration areas with putty or
heat insulating material (arranged in teh local field) as
shown in the figure below. If insects or litter enters the
outdoor unit, a short circuit in the electric parts box
may result.
Heat Insulation of piping: Make sure to insulate the
field pipings (on both liquid and gas lines) and refrig-
erant branching kit. If they are not insulated, water
leakage can result.
The maximum temperature of the piping on the gas
line is about 248
0
F during heating operation. Use an
insulation sufficiently resistant to this temperature.
Reinforce the refrigerant piping according to the
installation environment. If it is not reinforced, con-
CAUTION
densate may form on the surface of the insulation.
Make sure to insulate the field piping up to the piping
connection area inside the unit. If the piping is
exposed, dew condensation and contact burns can
result.
Pipe size
Tightening angle
(Guideline)
Recommended arm
length of tool (in.)
φ 3/8”
(9.5mm)
60°~90°
Approx. 7 7/8”
(197.62mm)
φ 5/8”
(15.88mm)
30°~60°
Approx. 11 13/16”
(300.04mm)
Page view 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 30 31

Comments to this Manuals

No comments