Installation EDUS39-606A-N
25 Installation of Outdoor Units
Transmission wiring connection procedure
If excessive force is applied while connecting a cable
to the terminal block on the PC board, the PC board
may be damaged.
A B C
ABCF1 F2 F1 F2
ABCF1 F1F2 F2
F1 F2 F1 F2 F1 F2
F1 F2 F1 F2
C/H SELECTOR
TO IN/D UNIT
TO OUT/D UNIT
A1P
Cool/heat
selector
Outdoor unit PC board (A1P)
Take care of the
polarity
Use the conductor
of sheathed wire
(2 wire) (no polarity)
Terminal board
(field supply)
Indoor unit
Setting the cooling/heating operation
TO IN/D
UNIT
F1 F2
DS1
1234
OFF
ON
O
U
T
I
N
F1 F2 P1 P2
P1 P2
Remote controller
Performing cool/heat setting with the remote controller connected
to the indoor unit.
Keep the cool/heat selector switch (DS1) on the outdoor unit PC
board (A1P) at the factory setting position on the indoor unit.
Performing cool/heat setting with the cool/heat selector.
Connect the cool/heat selector remote controller (optional) to the
A/B/C terminals and set the cool/heat selector switch (DS1) on the
outdoor unit PC board (A1P) to outdoor unit. .
CAUTION
For low-noise operation, you must install the optional
External Control Adaptor for the Outdoor Unit.
For details, see the installation manual attached to the adaptor.
Restrictions and Cautions for Wiring between
Units:
Make sure to observe the restrictions below. If they are
not observed, transmission error may occur.
Maximum wiring length: 3280 ft. (1000 m)
Total wiring length: 6560 ft. (2000 m) or less
Maximum number of branches: 5
Never connect 208-230V to the terminal block for the trans-
mission wiring.
Doing so will break the entire system.
The transmission wiring from the indoor units must be con-
nected to the F1/F2 ( to indoor unit) terminals on the PC
board in the outdoor unit.
Make sure to use sheathed two-core cables of AWG18..
Only the cool/heat selector remote controller can use a tri-
axial cable.
All cables used in the wiring between the units should
be procured on the site.
Up to 5 branches are available in the wiring between
units. However, sub-branching from a branch is not
allowed.
F2F1F2F1
F1 F2 F1 F2
F2F1
Branch
Sub-branch
after branch
A B C
A B C
DS1
1234
OFF
ON
O
U
T
I
N
Cool/heat selector