EDUS39-606A-N Installation
Installation of Outdoor Units 11
If the conventional refrigerant and refrigerator oil are mixed
in the R-410A, the refrigerant may deteriorated.
Never perform outdoor unit piping connection work
when it is raining.
The PCI Data Station is a class A product. In a domestic
environment this product may cause radio interference in
which case the user may be required to take adequate
measures.
4.2 Introduction
4.2.1 Combination
Always use an appropriate indoor unit compatible with R-
410A.
To learn which models of indoor units are compatible with
R-410A, refer to the product catalogs.
Total capacity/quantity of indoor units
<Outdoor unit> <Total capacity of indoor units> <Total quantity of indoor units>
RXYMQ36MVJU.... 18~46.8 6 units
RXYMQ48MVJU.... 24~62.4 8 units
4.2.2 Standard operation limit
The figures below assume following operating conditions for
indoor and outdoor units:
Equivalent pipe length ................25 ft. (7.6 m)
Level difference...........................0 ft.
Cooling Heating
<b>
B
<c>
A
C
D
<a>
–4
5
59
115
41
5050
43
70
95
81
50
23
77
60
67 8257
A Outdoor temperature (°FDB)
B Indoor temperature (°FWB)
C Outdoor temperature (°FWB)
D Indoor temperature (°FDB)
Range for continuous operation
Range for pull down operation
Range for warming up operation
Range for operation
4.2.3 Technical specifications
In the following table, <a> and <b> indicates the operating
condition:
Electrical specifications
<c> in the table indicates the operating condition shown in Sec-
tion 2-3, Technical specifications.
Accessories
Confirm that the following accessories are supplied:
Clamp Insulation tube Others
Operation manual
Installation manual
Optional accessories
To install the above outdoor units, use the following optional
parts:
Refrigerant branching kit*
NOTE: Systems using R-410A must have the appropriate
kit designed for that system.
REFNET joint KHRP26M22T
REFNET header KHRP26M22H KHRP26M33H
*Select the refrigerant branching kit in accordance with Sec-
tion 6. REFRIGERANT PIPING WORK.
Main components:
For main components and function of the main components,
refer to the Engineering Data Book.
4.3 Before Installation
Model
RXYMQ36MVJU RXYMQ48MVJU
Precau-
tion
Refrigerant
R-410A
Power
208-230V 60Hz
Cooling capacity
(MBh) 36 48 <a>
Heating capacity
(MBh) 40 54 <b>
Cooling input
(kW) 3.05 4.73 <a>
Heating input
(kW) 3.27 4.26 <b>
Dimensions
(inch) 52 15/16 × 35 7/16 × 12 5/8
H × W × D
Weight
(lb.) 310
Connections
Gas
(inch) 5/8
Liquid
(inch) 3/8
Model
RXYMQ36MVJU RXYMQ48MVJU
Precaution
Power
Phase ~
Frequency (Hz) 60
Voltage (V) 208-230
Voltage
torerance
(%) ±10
Rated current
of fuse
(A) 30
Compressor
Phase 3~
Frequency (Hz) 60
Voltage (V) 208-230
Min. Circuit
Amps.
(A) 27.0 <c>